VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-58
07-15 Gear Gap Acceleration-Interruption Time
a
Factory setting 0.00
Settings 0.00~400.00 Sec
07-16 Gear Gap Acceleration-Interruption Frequency
a
Factory setting 6.00
Settings 0.00~400.00Hz
07-17 Gear Gap Deceleration-Interruption Time
a
Factory setting 0.00
Settings 0.00~400.00 Sec
07-18 Gear Gap Deceleration-Interruption Frequency
a
Factory setting 6.00
Settings 0.00~400.00Hz
These parameters determine the time and frequency point for the drive to stop
acceleration or deceleration to allow the motor to catch up to the ac drives output
frequency. This is commonly used with heavy loaded applications where the motors
rotor is lagging the stator.
07-16
Gear Gap
Acceleration-
Interruption
Frequency
Gear Gap
Acceleration-
Interruption
Time
Gear Gap
Deceerationl-
Interruption
Time
07-18
Time
07-17
Gear Gap
Deceleration-
Interruption
Frequency
07-15
Gear Gap Acceleration/Deceleration
07-19 External Terminals RUN after Fault Reset
a
Factory setting 0
Settings 0 Invalid
1 If running command is still ON and it is running.
When RUN command terminal of external terminal is ON and AC drive solve the fault
after detecting fault, you can re-run by pressing RESET key.