VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-44
05-19 LC of Motor 2 Factory setting X
X
Settings MH
05-20 Iron Loss of Motor 2
a
Factory setting 1.5
Settings 0.0~10.0%
For parameters 05-11~20, please refer to parameters 05-01~05-10.
05-21 ASR (Auto Speed Regulation) P (Gain) 1
a
Factory setting 25.0
Settings 0.0~500.0%
This parameter determines the error value gain while in vector, or vector w/PG control
mode.
05-22 ASR I (Integration) Time 1
a
Factory setting 0.250
Settings 0.000~10.000 sec
0.000: no integration
This parameter determines the integration time during vector or vector w/PG control.
There is no integration, if the integration time is set to 0.
05-23 ASR P (Gain) 2
a
Factory setting 25.0
Settings 0.0~500.0%
This setting determines the gain of the error value, and it is suitable for use with the vector
control and the PG control.
05-24 ASR I (Integration) Time 2
a
Factory setting 0.250
Settings 0.000~10.000 sec
0.000: no integration
This setting is defined as the integration time of the integrating device, and it is suitable
for use with the vector control and the PG control.
The integration is invalid if the integration time is set as 0.
05-25 Frequency Switch between ASR1 and 2
a
Factory setting 7.00
Settings 0.0~400.00Hz
This parameter is defined as the frequency switching point between ASR1 (Pr. 05-21, 22)
and ASR2 (Pr. 05-23, 24).
F
PI
+
-
+
-
H
Speed Feedback