8
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-21
Group 6: Protection Parameter
Control Mode
Parameters Functions Settings
Factory
Setting
VF VG SV SG T TG
a
06-00 Low Voltage Level
160-220V
320-440V
180
360
{ { { { { {
a
06-01
Over-Voltage
Stall Prevention
350.0-450.0V
700.0-900.0V
380.0
760.0
{ { { { ° °
a
06-02
Phase-Loss
Protection
0: warn and keep operating
1: warn and ramp to stop
2: warn and coast to stop
0
{ { { { { {
a
06-03
Over-Current Stall
Prevention during
Acceleration
10~250% 170
{ { { { ° °
a
06-04
Over-Current Stall
Prevention during
Operation
10~250% 170
{ { { { ° °
a
06-05
Over-Current
Deceleration Time
during Operation
0.05~600.00 Sec 3.00
{ { { { ° °
a
06-06
Over-Torque
Detection
Selection (oL2)
0: disabled
1: Over-torque detection during
constant speed operation,
continue to operate after
detection.
2: Over-torque detection during
constant speed operation,
stop operation after detection.
3: Over-torque detection during
entire (acceleration, steady
state, deceleration) operation,
continue operation after
detection.
4: Over-torque detection during
entire (acceleration, steady
state, deceleration) operation,
stop operation after detection.
0
{ { { { { {
a
06-07
Over-Torque
Detection Level
(oL2)
10~250% 150
{ { { { { {
a
06-08
Over-Torque
Detection Time
(oL2)
0.0~60.0 Sec 0.1
{ { { { { {