These parameters determine Dwell (sleep) functions of the AC drive. If the command
frequency falls below the Dwell frequency, for the specified time in Pr. 08-12, then the
drive will shut off the output and wait until the command frequency rises above Pr. 08-11.
Please see the below diagram.
08-11
08-10
08-12
0Hz
Dwell (sleep) Function
Dwell (sleep) Period
Dwell (sleep) Frequency
Revival Frequency
Frequency Command
ctual running
output frequency
08-13
Fan control
a
Factory setting 0
Settings
0 When power is applied, the fan will turn on
1 When the run command is given, the fan will turn on