3. Technical data
3.1 General t
echnical data
Table 1
General technical data
Characteriscs
Units 3000 1200 1200T 1200TX
600
600T
200
200T
Dimensions (L x W x H) mm
1000 x
517
x 965
695 x 286 x 704
695 x 286
x
467
Mass (not including
packaging)
kg 570 245 145
Noise level (at ulmate) dB (A) < 65 < 63
Vibraon test limit at in-
le
t
mm s
-1
< 1.5
Inial force to push the
pump
kg < 20.0
Sus
tained force to push
the pump
kg < 10.0
Warm-up me to nomi-
nal pumping perform-
ance
hours 0.75 3
0.75
3 (T variant)
Performance
Typical peak pumping
speed (no gas pur
ge/
cold pump)
m
3
h
-1
2800 1030 930 600 200
Average ulmate pressure
No gas purge mbar 0.001 0.0015
At 44 slpm purge ow mbar 0.0015 0.005 0.01
At 96 slpm purge ow mbar 0.003 0.02 -
Ulmate pressure test limit
No gas purge
mbar 0.005
At 44 slpm purge
ow
mbar 0.005 0.01 0.05
At 96 slpm purge
ow
mbar 0.01 0.05 - - - -
Connecons
Pump inlet ange ISO200 ISO100 ISO100 ISO100 ISO100 ISO63
Exhaus
t gas outlet NW40 NW25 NW25 NW25 NW25 NW25
3.2 Operang and storage condions
10/2020 - ©Edwards Limited
Page 13M56635880_D
M56635880_D - Technical data