Prox Active
Proximity Active (PROX_ACTIVE [74.5]) displays
which of the following Proximity Alerts are active:
Travel Open—Active if the Travel is greater than the
Travel Open Alert Point.
Travel Closed—Active if the Travel is lower than the
Travel Closed Alert Point.
Proximity Hi Hi—Active if the Travel is greater than the
Proximity Hi Hi Alert Point.
Proximity Hi—Active if the Travel is greater than the
Proximity Hi Alert Point.
Proximity Lo—Active if the Travel is lower than the
Proximity Lo Alert Point.
Proximity Lo Lo—Active if the Travel is lower than the
Proximity Lo Lo Alert Point.
Prox Enable
Proximity Enable (PROX_ENABLE [75.5]) permits
enabling or disabling the Proximity Alerts shown
above.
Prox Config
(TB > Detailed Setup > Alerts >Tvl and Prox > Prox
Config)
Tvl Open Alrt Pt
Travel Open Alert Point (TVL_OPEN_ALRT_PT
[77.8]) is the value of the travel in percent (%) or
ranged travel, which, when exceeded, sets the Travel
Open Alert.
Tvl Open DB
Travel Open Deadband (TVL_OPEN_DB [77.9]) is the
travel in percent (%) of ranged travel required to clear
a Travel Open alert, once it has been set.
Tvl Closed Alrt Pt
The Travel Closed Alert is set when the value of the
travel, in percent (%) of ranged travel, goes below the
Travel Closed Alert Point (TVL_CLOSED_ALRT_PT
[77.10]).
Tvl Closed DB
Travel Closed Deadband (TVL_CLOSED_DB [77.11])
is the travel in percent (%) of ranged travel required to
clear a Travel Closed alert, once it has been set.
Tvl History Active
Travel History Active (TVL_HISTORY_ACTIVE [74.6])
displays which of the following Travel History Alerts
are active:
Cycle Count—Active when the Cycle Count exceeds
the Cycle Count Alert Point.
Travel Accum—Active when the Travel Accum
exceeds the Travel Accumulator Alert Point.
Tvl History Enable
Travel History Enable (TVL_HISTORY_ENABLE
[75.6]) permits enabling or disabling the Travel History
Alerts shown above.
Tvl History Config
(TB > Detailed Setup > Alerts >Tvl and Prox > Tvl
History Config)
Cycle Count
The Cycle Counter (CYCLE_COUNT [73]) records the
number of times the travel changes direction. The
change in direction must occur after the deadband has
been exceeded before it can be counted as a cycle.
See figure 5-6. You can reset the Cycle Counter by
configuring it as zero.
Cycle Count Alrt Pt
Cycle Counter Alert Point
(CYCLE_COUNT_ALRT_PT [77.6]) is the value of the
Cycle Counter, in cycles, which, when exceeded, sets
the Cycle Counter Alert.
Cycle Count DB
Cycle Counter Deadband (CYCLE_COUNT_DB
[77.7]) is the area around the travel reference point, in
percent (%) of ranged travel, that was established at
the last increment of the Cycle Counter. This area
must be exceeded before a change in travel direction
can be counted as a cycle. See figure 5-6.
Travel Accum
Travel Accumulator (TRAVEL_ACCUM [72]) records
the total change in travel, in percent (%) of ranged
travel, since the accumulator was last cleared. The
value of the Travel Accumulator increments when the
magnitude of the change exceeds the Travel
Accumulator Dead-band. See figure 5-7. You can
reset the Travel Accumulator by configuring it to zero.
Tvl Accum Alrt Pt
Travel Accumulator Alert Point
(TVL_ACCUM_ALRT_PT [77.4]) is the value of the
Travel Accumulator, in percent (%) of ranged travel,