DVC6000f Series
March 2006
5-24
Figure 5-1. Feedback Connection for Typical Sliding-Stem
Actuator (Up to 4-inch Travel)
ACTUATOR
STEM
TRAVEL SENSOR SHAFT
FEEDBACK ARM
CONNECTOR ARM
ADJUSTMENT ARM
changed to Travel with Pressure Fallback/Auto
Recovery.
Zero Pwr Cond
Zero Power Condition (ZERO_PWR_COND [42.2])
identifies whether the valve is open or closed when
instrument power is lost. If you are unsure how to set
this parameter, disconnect the segment loop power to
the instrument. The resulting valve travel is the Zero
Power Condition.
Tvl Cutoff Lo
Travel Cutoff Lo (FINAL_VALUE_CUTOFF_LO [16])
defines the low cutoff point for travel, in percent.
Below this cutoff, the travel target is set to 23%. A
travel cutoff of 0.5% is recommended to help ensure
maximum shutoff seat loading. Travel Cutoff Lo is
effectively deactivated by setting it to 25%.
Actuator Style
Select the Actuator Style (ACTUATOR_STYLE
[42.1]), spring & diaphragm, piston double-acting
without spring, piston single-acting with spring, or
piston double-acting with spring.
CAM
ROLLER
29B1665-A / DOC
STEM
CONNECTOR
Figure 5-2. Feedback Connection for Typical Long-
Stroke Sliding-Stem Actuator (4 to 24-Inches Travel)
Relay Type
Enter the Relay Type (RELAY_TYPE [42.5]), A or B,
installed in the digital valve controller. Relay A is for
double-acting and single-acting direct-acting
applications. Relay B is used for single-acting
reverse-acting applications.
Feedback Conn
Select the Feedback Connection(FEEDBACK_CONN
[42.4]), Rot-All, SS-roller, or SStem-Standard. For
rotary valves, enter Rot - All, SS-Roller. For
sliding-stem valves, if the feedback linkage consists of
a connector arm, adjustment arm, and feedback arm,
similar to the linkage shown in figure 5-1, enter SStem
- Standard. If the feedback linkage consists of a roller
that follows a cam, similar to the linkage shown in
figure 5-2, enter Rotary All, SStem - Roller.
Tvl Sen Motion
Note
The Travel Sensor Motion is set
automatically by the Setup Wizard, or
during the Auto Calibration procedure.
Select Clockwise or Counterclockwise. Travel Sensor
Motion (TRAVEL_SEN_MOTION [42.3]) establishes
the proper valve travel sensor (feedback) rotation.
5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher Fieldvue DVC6010f and is the answer not in the manual?

Emerson Fisher Fieldvue DVC6010f Specifications

General IconGeneral
BrandEmerson
ModelFisher Fieldvue DVC6010f
CategoryController
LanguageEnglish

Related product manuals