OS Function Block
March 2006
5-117
Figure 5-20. Split Range and Sequence Operation
(X
11
, Y
11
)
SP
Split Range Sequencing
(X22 , Y22)
(X
12
, Y
12
)
OUT_1
OUT_2
0%
50% 100%
100%
100%
OUT_2
OUT_1
100%
0% 0%
0% 50%
(X
12
, Y
12
)(X
22
, Y
22
)
(X
11
, Y
11
)
(X
21
, Y
21
)(X
21
, Y
21
)
SP
X
X
Y
Y
Figure 5-21. OUT with LOCKVAL True
0%
SP
OUT
1
OUT 2
OUT
1 remains at
end point when OUT_2
is non-zero
50%
100%
Refer to figure 5-21 for an example of LOCKVAL =
true, and figure 5-22 for an example of LOCKVAL =
false. The parameter LOCKVAL provides an option to
specify whether OUT_1 remains at its ending level
when control is switched to OUT_2, or goes to Y
11
. If
LOCKVAL is true, OUT_1 remains at its ending value
when X is greater than X
12
. If LOCKVAL is false, then
OUT_1 goes to Y
11
when X is greater than X
12
.
Some hysteresis in the switching point may be
required because the output may change by a full
stroke of the valve. HYSTVAL [12] contains the
amount of hysteresis. If X < = X12HYSTVAL,
OUT_1 may be determined by the calculated y value.
If X12HYSTVAL < X < X12 and X has not reached
X12 since it was less than X12HYSTVAL, OUT_1
may be determined by the calculated y value. If
X12HYSTVAL < X < X12 and X has reached X12
since it was less than X12HYSTVAL, OUT_1 may be
determined by the LOCKVAL setting. If X12 < X,
OUT_1 may be determined by the LOCKVAL setting.
Figure 5-22. OUT with LOCKVAL False
OUT 1 OUT 2
0%
SP
50%
100%
OUT_1 goes to zero
OUT_2 becomes
Initialization and Back Calculation
Requirements
Refer to figure 5-23, Output Splitter Configuration,
where:
PID1 = Upstream driving controller or function block.
Splitter = Split range function block being described.
AO = Receiver of OUT_1 for 050% range of SP
PID2 = Receiver of OUT_2 for 50100% range of SP
CAS_IN of the Splitter receives the OUT of PID1.
BKCAL_IN of PID1 receives BKCAL_OUT of the
Splitter. CAS_IN of the AO receives OUT_1 of the
Splitter and PID2 receives OUT_2 of the Splitter.
BKCAL_IN_1 of the Splitter receives BKCAL_OUT of
the AO and BKCAL_IN_2 of the Splitter receives
BKCAL_OUT of PID2.
5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher Fieldvue DVC6010f and is the answer not in the manual?

Emerson Fisher Fieldvue DVC6010f Specifications

General IconGeneral
BrandEmerson
ModelFisher Fieldvue DVC6010f
CategoryController
LanguageEnglish

Related product manuals