Transducer Block
March 2006
5-59
Table 5-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial ValueRangeMode
RO /
RW
Index
Number
SPEC_SHEET_ACT
85
Actuator Size
ACTUATOR SIZE
85.1 RW ALL NULL ALL Data Type: Visible String
Effective Area
EFFECTIVE AREA
85.2 RW ALL 0.00 ALL Data Type: Float
Air
AIR
85.3 RW ALL
1=open
2=close
1=open ALL Data Type: Enum
Lower Bench Set
LOWER_BENCH_SET
85.4 RW ALL 0.00 ALL Data Type: Float
Upper Bench Set
UPPER_BENCH_SET
85.5 RW ALL 0.00 ALL Data Type: Float
Nominal Supply Pressure
NOMINAL_SUPPLY_PRESSURE
85.6 RW ALL 0.00 ALL Data Type: Float
Spring Rate
SPRING_RATE
85.7 RW ALL 0.00 ALL Data Type: Float
Stroking Time Open
STROKING_TIME_OPEN
85.8 RW ALL 0.00 ALL
Data Type: Float
Seconds
Stroking Time Close
STROKING_TIME_CLOSE
85.9 RW ALL 0.00 ALL
Data Type: Float
Seconds
Lever Style
LEVER_STYLE
85.10 RW ALL
1=Pivot Point
2=Rack & Pinion
1=Pivot Point ALL Data Type: Enum
Moment Arm
MOMENT_ARM
85.11 RW ALL 0.00 ALL Data Type: Float
DEVICE_RECORD
86
These parameters can only set by
a new reserved AI command.
Temp Max
TEMP_MAX
86.1 RO N/A 9999.99 N/A
Data Type: Float
Highest temperature recorded
Temp Max Time
TEMP_MAX_TIME
86.2 RO N/A Zero time N/A Data Type: Time Value
Temp Min
TEMP_MIN
86.3 RO N/A 9999.99 N/A
Data Type: Float
Lowest temperature recorded
Temp Min Time
TEMP_MIN_TIME
86.4 RO N/A Zero time N/A Data Type: Time Value
Supp Press Max
SUPP_PRESS_MAX
86.5 RO N/A 0.0 N/A
Data Type: Float
Highest supply pressure recorded
Supp Press Max Time
SUPP_PRESS_MAX_TIME
86.6 RO N/A Zero time N/A Data Type: Time Value
Supp Press Min
SUPP_PRESS_MIN
86.7 RO N/A 9999.99 N/A
Data Type: Float
Lowest supply pressure recorded
Supp Press Min Time
SUPP_PRESS_MIN_TIME
86.8 RO N/A Zero time N/A Data Type: Time Value
Comm Error Count
COMM_ERROR_COUNT
86.9 RW N/A 0 SETUP Not used by the DVC6000f
Protection
PROTECTION
87 RW ALL
1=None
2=Calibration
3=Setup & Calibration
4=All
2=Calibration NONE
Data Type: Enum
Write lock enable/disable. If setting
is at or above a parameters
protection level then that parameter
is read-only.
PERF_DIAG
88
PD Run
PD_COMMAND
88.1 RW
AUTO
MAN
N
1=PD On
2=PD Off
1=PD On NONE
Data Type: Enum
Controls whether PD will run or not.
PD Status
PD_STATUS
88.2 RO ALL
1=Not Running
2=Running
NONE
Data Type: Enum
Status of performance diagnostics.
PD Config
PD_CONFIG
88.3 RW ALL 0 NONE
Data Type: Bit String
Bit string for configuring PD setup
and options.
PD Extra
PD_EXTRA
88.4 RW ALL 0 NONE
Data Type: Uint32
Extra 32 bit integer for sending
values to PD.
Continued
5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher Fieldvue DVC6010f and is the answer not in the manual?

Emerson Fisher Fieldvue DVC6010f Specifications

General IconGeneral
BrandEmerson
ModelFisher Fieldvue DVC6010f
CategoryController
LanguageEnglish

Related product manuals