OS Function Block
March 2006
5-121
Table 5-47. Output Splitter Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Initial
Value
Range
Block
Mode
RO /
RW
Index
Number
Output 2 Range
OUT_2_RANGE
11 RO
EU at 100%
EU at 0 %
Unit Index
Decimal Point
100
0
%
2
Data Type: DS-68
The high and low scale values, engineering units code,
and number of decimal places to be used in displaying the
OUT value, this parameter has not effect on this block.
Grant Deny
GRANT_DENY
12
Data Type: DS-70
Options for controlling access of host computers and local
control panels to operating, tuning, and alarm parameters
of the block. GRANT:0=N/A, 1=granted
DENY: 0=N/A, 1= denied
GRANT
12.1 N/A
0: Program
1: Tune
2: Alarm
3: Local
All bits: 0
DENY
12.2 N/A All bits: 0
Status Options
STATUS_OPTS
13 OOS
1: IFS if BAD
CAS_IN
All bits: 0
Data Type: Bit String
0=Disabled 1=Enabled
User option for status
Cascade Input
CAS_IN
14
Status
BAD:
NC:
const
Data Type: DS-65
The remote setpoint from another block.
Value 0
Back Calculation Output
BKCAL_OUT
15 RO Status Limits
Data Type: DS-65
Output value to another block for backwards output
tracking.
Input Array
IN_ARRAY
16 All: 0
Data Type: Float
Used with OUT_ARRAY to map input to output. See
FF892 3.2.2.
Output Array
OUT_ARRAY
17 All: 0
Data Type: Float
Used with IN_ARRAY to map input to output. See FF892
3.2.2.
Lockval
LOCKVAL
18
0=Undfined
1=no lock
2=lock
0=
Undefined
Data Type: Enum
Used with OUT_ARRAY to map input to output. See
FF892 3.2.2.
Back Calculation Input 1
BKCAL_1_IN
19
Status
BAD:
NC:
const
Data Type: DS-65
The value and status reflecting the BKCAL_OUT of the
lower block associated with OUT_1. It is used for
initialization and to prevent windup in upstream blocks.
Value 0
Back Calculation Input 2
BKCAL_2_IN
20
Status
BAD:
NC:
const
Data Type: DS-65
The value and status reflecting the BKCAL_OUT of the
lower block associated with OUT_2. It is used for
initialization and to prevent windup in upstream blocks.
Value 0
Balance Time
BAL_TIME
21 Positive 0
Data Type: Float
Specifies the time for the internal working value of bias or
ratio to return to the operator set bias or ratio, in seconds.
Hystval
HYSTVAL
22
Update Event
UPDATE_EVT
23 RO N/A
Data Type: DS-73
This alert is generated by any change to the static data.
UNACKNOWLEDGED 23.1 RW N/A
0=Undefined
1
=Acknowledged
2
=Unacknowledged
0=
Undefined
UPDATE STATE
23.2 RO N/A
0=Undefined
1
=Update Reported
2
=Updated not
reported
0=
Undefined
TIME_STAMP
23.3 RO N/A 0
STATIC_REVISION
23.4 RO N/A 0
RELATIVE_INDEX
23.5 RO N/A 0
−Continued−