DVC6000f Series
March 2006
5-46
Table 5-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial ValueRangeMode
RO /
RW
Index
Number
PRESS_CAL
46
Supp Press Scale
SUPP_PRESS_SCALE
46.1 RW
MAN
OOS
> = 0 1 CAL Data Type: Float
Supp Press Offset
SUPP_PRESS_OFFSET
46.2 RW
MAN
OOS
0 to 16383 0 CAL Data Type: Uint16
Press A Scale
PRESS_A_SCALE
46.3 RW
MAN
OOS
> = 0 1 CAL Data Type: Float
Press A Offset
PRESS_A_OFFSET
46.4 RW
MAN
OOS
0 to 16383 0 CAL Data Type: Uint16
Press B Scale
PRESS_B_SCALE
46.5 RW
MAN
OOS
> = 0 1 CAL Data Type: Float
Press B Offset
PRESS_B_OFFSET
46.6 RW
MAN
OOS
0 to 16383 0 CAL Data Type: Uint16
Press IP Bias
PRESS_IP_BIAS
46.7 RW
MAN
OOS
0100% 70% CAL Data Type: Float
Press MLFB Bias
PRESS_MLFB_BIAS
46.8 RW
MAN
OOS
0100% 50% CAL Data Type: Float
PRESS_TUNE
47
Press Cutoff Hi
PRESS_CUTOFF_HI
47.1 RW
MAN
OOS
25 125%,
> CUTOFF_LO
99.50% SETUP Data Type: Float
Press Cutoff Lo
PRESS_CUTOFF_LO
47.2 RW
MAN
OOS
25 125% <
CUTOFF_HI
0.50% SETUP Data Type: Float
Press Prop Gain
PRESS_PROP_GAIN
47.3 RW
MAN
OOS
> = 0, < 32 2.2 SETUP
Data Type: Float
Proportional gain
Press Integ Gain
PRESS_INTEG_GAIN
47.4 RW
MAN
OOS
> = 0, < 32 0.1 SETUP
Data Type: Float
Integral resets per second
Press Rate Gain
PRESS_RATE_GAIN
47.5 RW
MAN
OOS
> = 0, < = 512 0 SETUP
Data Type: Float
Derivative gain
Press Integ DeadZ
PRESS_INTEG_DEADZ
47.6 RW
MAN
OOS
= 0%, < = 2.0% 0.25% SETUP
Data Type: Float
Integrator Deadzone, 1/2 width
Press Integ Hi Lim
PRESS_INTEG_HI_LIM
47.7 RW
MAN
OOS
> = 0%, < = 100%,
>INTEG_LO
20% SETUP
Data Type: Float
Integrator limits
Press Integ Lo Lim
PRESS_INTEG_LO_LIM
47.8 RW
MAN
OOS
< = 0%, > = 100%,
<INTEG_HI
20% SETUP
Data Type: Float
Integrator limits
Press Integ IC Hi
PRESS_INTEG_IC_HI
47.9 RW
MAN
OOS
>= 100%, < = 100% 12% Not used by the DVC6000f
Press Integ IC Lo
PRESS_INTEG_IC_LO
47.10 RW
MAN
OOS
>= 100%, < = 100% 12% Not used by the DVC6000f
Press MLFB Gain
PRESS_MLFB_GAIN
47.11 RW
MAN
OOS
> 0, < = 100 35 SETUP Data Type: Float
Temperature
TEMPERATURE
48 RO N/A N/A N/A
Data Type: Float
Electronics temperature Controls
AI channel 11
Target Travel
TRAVEL_TARGET
49 RO
Status
STATUS
49.1 RO
MAN
OOS
N/A
Data Type: DS-65
In Travel Control: Setpoint for valve
travel in %, post characterization.
In Pressure Control:
Setpoint for
implied valve travel as a % or
pressure range, post
characterization.
Value
VALUE
49.2 RO
MAN
OOS
N/A
Input Char
INPUT_CHAR
50 RW
MAN
OOS
1=Linear
2=Equal %
3=Quick Opening
4=Reserved
5=Custom
1=Linear SETUP Data Type: Enum
Continued
5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher Fieldvue DVC6020f and is the answer not in the manual?

Emerson Fisher Fieldvue DVC6020f Specifications

General IconGeneral
BrandEmerson
ModelFisher Fieldvue DVC6020f
CategoryController
LanguageEnglish

Related product manuals