DVC6000f Series
March 2006
3-2
Figure 3-1. Model 375 Field Communicator
ALPHANUMERIC
KEYS
IrDA INTERFACE
(TOP)
HART AND fieldbus
COMMUNICATION
TERMINALS (TOP)
TOUCH SCREEN
DISPLAY
NAVIGATION KEYS
(FOUR ARROW KEYS)
TAB KEY
ON/OFF KEY
MULTIFUNCTION LED
BACKLIGHT
ADJUSTMENT
KEY
POWER SUPPLY
CHARGER
CONNECTION (SIDE)
FUNCTION KEY
ENTER KEY
STYLUS
(BACK)
OPTIONAL
EXPANSION
PORT (SIDE)
DVC6000f: Tag
1 Setup & Diag
3 Travel 53.69%
4 Valve SP 52.6%
5 Drive Sgl 58.15%
SCRATCH
PAD
Note
The Model 375 Field Communicator
device description revision (DD)
determines how the Field
Communicator interfaces with the
instrument. For information on
displaying the device description
revision, see page 3-7.
This section discusses the display, keypad, and menu
structure for the Field Communicator, shown in figure
3-1. It includes information for displaying the Field
Communicator device description revision number. For
information on connecting the Field Communicator to
the instrument, see the Installation section, Section 2.
For more information on the Field Communicator, such
as specifications and servicing, see the User’s Manual
for the Field Communicator 00375-0047-0001,
included with the Field Communicator. This manual
also is available from Rosemount Inc., Measurement
Division.
Display
The Field Communicator communicates information to
you through a 1/4 VGA (240 by 320 pixels)
monochrome touch screen. It has a viewing area of
approximately 9 cm by 12 cm.
Using the Keypad
On/Off Key
The on/off key is used to turn the Field Communicator
on and off.
From the Main Menu, select F
OUNDATION Fieldbus
Application to run the fieldbus application. If a live
fieldbus device is connected to the Field
Communicator, the Fieldbus Application Menu will
display briefly, followed by the Live Device List.
If insufficient voltage is detected, a warning will appear
on the Field Communicator saying “no FF Segment
Voltage Detected”. Press OK to go to the FF Main
Menu.
The on/off key is disabled while any applications are
open, making it necessary for you to exit the 375 Main
Menu before using the on/off key. This feature helps to
avoid situations where the Field Communicator could
be unintentionally turned off while a device’s output is
fixed or when configuration data has not been sent to
a device.
Navigation Keys
Four arrow navigation keys allow you to move through
the menu structure of the application. Press the right
arrow (
) navigation key to navigate further into the
menu.
3