DVC6000f Series
March 2006
5-32
transducer block target mode to Manual or Auto. In
any case, the target mode will remain Out of Service,
if the condition that caused the shutdown remains or
while until the shutdown trigger is disabled.
Enviro Active
Environment Active (ENVIRO_ACTIVE [74.3])
displays which of the following Environment Alerts are
active:
Supply Pressure Hi—Active if the supply pressure is
greater than the Supply Pressure Hi Alert Point
Supply Pressure Lo—Active if the supply pressure is
lower than the Supply Pressure Lo Alert Point
Temperature Hi—Active if the temperature is greater
than the Temperature Hi Alert Point
Temperature Lo—Active if the temperature is lower
than the Temperature Lo Alert Point
Enviro Enable
Environment Enable (ENVIRO_ENABLE [75.3])
permits enabling or disabling the Environment Alerts
shown above.
Supply Press Sensor Config
(TB > Detailed Setup > Alerts > Sensor and Enviro >
Supply Press Sensor Config)
Supply Press
Supply Pressure (SUPPLY_PRESSURE.VALUE
[35.2]) displays the instrument supply pressure in kPa,
bar, or psi.
Supply Press Hi Alrt Pt
When supply pressure exceeds the Supply Pressure
Hi Alert Point (SUP_PRES_HI_ALRT_PT [76.8]) the
Supply Pressure Hi Alert is active.
Supply Press Lo Alrt Pt
When supply pressure is lower than the Supply
Pressure Lo Alert Point (SUP_PRES_LO_ALRT_PT
[76.9]) the Supply Pressure Lo Alert is active.
Temp Sensor Config
(TB > Detailed Setup > Alerts > Sensor and Enviro >
Temp Sensor Config)
Temperature
Degrees Fahrenheit or Celsius. The temperature
(TEMPERATURE [48]) is measured from a sensor
mounted on the digital valve controller’s printed wiring
board.
Temp Hi Alrt Pt
When the instrument temperature exceeds the
Temperature Hi Alert Point (TEMP_HI_ALRT_PT
[76.6]) the Temperature Hi Alert is active.
Temp Lo Alrt Pt
When the instrument temperature is lower than the
Temperature Lo Alert Point (TEMP_LO_ALRT_PT
[77.7]) the Temperature Lo Alert is active.
Tvl and Prox
(TB > Detailed Setup > Alerts > Tvl and Prox)
Note
The alerts contained in this section are
valid for both travel and pressure
control.
Tvl Active
Travel Active (TRAVEL_ACTIVE [74.4]) displays
which of the following Travel Alerts are active:
Travel Deviation—Active if the Travel deviation
exceeds the Travel Deviation Alert Point by more than
the Travel Deviation Time.
Travel Limit Hi Hi—Active if the Travel exceeds the
Travel Limit Hi Hi Alert point.
Travel Limit Hi—Active if the Travel exceeds the
Travel Limit Hi Alert point.
Travel Limit Lo—Active if the Travel is lower than the
Travel Limit Lo Alert point.
Travel Limit Lo Lo—Active if the Travel is lower than
the Travel Limit Lo Lo Alert point.
Travel Enable
Travel Enable (TRAVEL_ENABLE [75.4]) permits
enabling or disabling the Travel Alerts shown above.