EasyManuals Logo
Home>Emerson>Controller>Fisher Fieldvue DVC6020f

Emerson Fisher Fieldvue DVC6020f User Manual

Emerson Fisher Fieldvue DVC6020f
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #113 background imageLoading...
Page #113 background image
Transducer Block
March 2006
5-47
Table 5-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial ValueRangeMode
RO /
RW
Index
Number
Custom Points
CUSTOM_POINTS
51 RW
MAN
OOS
Linear, Y=X SETUP
Data Type: UINT16 Array[43]
Each item 2500 to 12500
First integrator is number of valid
points. Followed by 21 X values
and then 21 Y values.
X values must be increasing.
Y values must be increasing or
same.
Tvl Deviation
TRAVEL_DEVIATION
52 RO N/A 0 to 100% N/A
Data Type: Float
Absolute value of
(TRAVEL_TARGET [34]
TRAVEL), Controls AI channel 10
Drive Signal
DRIVE_SIGNAL
53 RO N/A 0 to 100% N/A
Data Type: Float
Controls AI channel 9
Drive Current
DRIVE_CURRENT
54 RO N/A 0 to 100% N/A Data Type: Float
MLFB
MLFB
55 RO N/A 100% to 100% N/A Data Type: Float
Failed Alarm
FAILED_ALM
56
Data Type: DS-71
Used to report alerts to host
system.
UNACKNOWLEDGED 56.1 RW ALL
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined NONE
ALARM_STATE 56.2 RO N/A
0=Undefined
1=Clearreported
2=Clearnot reported
3=Activereported
4=Activenot reported
0=Undefined N/A
TIME_STAMP 56.3 RO N/A 0 N/A
SUBCODE 56.4 RO N/A 0 N/A
VALUE 56.5 RO N/A 0 N/A
Data Type: Float
Value of parameter at alarm time
for single alarm, 0 for multiple
alarms
Maint Alarm
MAINT_ALM
57
Data Type: DS-71
Used to report alerts to host
system
UNACKNOWLEDGED 57.1 RW N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined NONE
ALARM_STATE 57.2 RO N/A
0=Undefined
1=Clearreported
2=Clearnot reported
3=Activereported
4=Activenot reported
0=Undefined N/A
TIME_STAMP 57.3 RO N/A 0 N/A
SUBCODE 57.4 RO N/A 0 N/A
VALUE 57.5 RO N/A 0 N/A
Data Type: Float
Value of parameter at alarm time
for single alarm, 0 for multiple
alarms
Continued
5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher Fieldvue DVC6020f and is the answer not in the manual?

Emerson Fisher Fieldvue DVC6020f Specifications

General IconGeneral
BrandEmerson
ModelFisher Fieldvue DVC6020f
CategoryController
LanguageEnglish

Related product manuals