COMMISSIONING
REV6 /REV7 OI 248 (EN) 47
7.2.1 Establish Gas Connections between Density Monitor and Pole columns
We recommend that the following tools be used to connect the gas
couplings:
- T022: Compact open-end wrench (open-ended spanner),
SW27
- WK001: Torque wrench (spanner) with ratchet adapter and
SW27 open-end wrench head
Remove the protective caps from the gas couplings on the pole
columns and the gas piping.
Grease the threads of the gas couplings as per L4.
Connect the gas piping to all pole columns. The filling
connections are equipped with threads for this purpose. First
screw on the filling connections by hand, then tighten
provisionally using tool T022, and finally tighten using tool set
WK001 to a torque of 30 Nm. Use two wrenches for connecting
the filling connections.
Retighten all couplings in the gas piping system.
In one equipment version, the switchgear is available with a gas
connection of type FlexLink.
The FlexLink technology makes it particularly easy to couple the
gas connections to the pole columns. (see Chapter “12.2” on
page 101)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE GL 313 F3/4031 P/VR and is the answer not in the manual?

GE GL 313 F3/4031 P/VR Specifications

General IconGeneral
BrandGE
ModelGL 313 F3/4031 P/VR
CategoryCircuit breakers
LanguageEnglish

Related product manuals