TROUBLESHOOTING
REV6 /REV2 OI 248 (EN) 57
8 Troubleshooting
8.1 Electrical Switching Commands Are Not Correctly Executed
Check the control voltage.
Check the gas pressure on the density monitor. If the gas
pressure is UW2 or less, no switching commands will be
executed.
Check the charging state of the closing spring. If the closing
spring is not charged, no closing operations can be carried out. It
is possible that a motor protection switch has tripped and
disconnected the charging motor from the power supply.
Check the shunt releases. Replace defective coils, determine the
cause of a potential overload and eliminate the cause.
Check the terminal connections to make sure they are tight and
properly connected.
Check the contactors in the faulty control circuit.
Check the electric operating points of the density monitor.
Work on the control system involves the danger of electric shock.
Sudden movements of the charging system or the breaker linka-
ge can cause serious injury.
Troubleshooting tasks should be handled by qualified staff only.
Such staff must follow the safety rules of electrical engineering.
DANGER

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE GL 313 F3/4031 P/VR and is the answer not in the manual?

GE GL 313 F3/4031 P/VR Specifications

General IconGeneral
BrandGE
ModelGL 313 F3/4031 P/VR
CategoryCircuit breakers
LanguageEnglish

Related product manuals