COMMISSIONING
REV6 /REV7 OI 248 (EN) 53
7.6.5 Checking Manual Operation
The manual operating levers are protected against accidental ope-
ration by a locking plate.
Loosen the locking bolts (1) one full turn and push the locking
plate (2) down and to the left.
Carry out one closing operation and one opening operation using
the manual operating levers. The circuit breaker will immediately
carry out the corresponding operation.
Push the locking plate up and to the right, and tighten the two
locking bolts again.
Manual operation bypasses any circuit breaker interlock system.
Therefore:
- Make sure that the gas pressure in the circuit breaker cor-
responds at least to the UW2 value before beginning ma-
nual operation.
WARNING
1 Locking bolt -
2 Locking plate -
3 Manual operation for closing operation -
4 Manual operation for opening operation -
2
4
1
1
3
BA-P-HANDSPERRE