TROUBLESHOOTING
REV6 /REV2 OI 248 (EN) 63
8.3 Replacing the Density Monitor
The density monitor (1) is connected to the filler block (3) by the
threaded bushing (2). The O-ring (4) seals the connection.
The internal thread (female thread) of the threaded bushing is a
right-hand thread, whereas the external thread (male thread) is a
left-hand thread.
If no density monitor is attached, the check valve (5) closes the ho-
le in the filler block. This makes it possible to replace the density
monitor without disconnecting the gas couplings from the pole co-
lumns.
Hold the density monitor firmly and unscrew and remove the
threaded bushing from the filler block (left-hand thread).
Because of the left-hand and right-hand thread combination, the
density monitor will move out of the threaded bushing
simultaneously.
Remove the threaded bushing (2) from the old density monitor.
Replace the O-ring (4). Lubricate the O-ring and sealing surfaces
as per L5.
Lubricate both threads of the threaded bushing as per L4.
Screw the threaded bushing two full turns onto the new density
monitor.
Place the threaded bushing and density monitor on the filler
block. Align the density monitor and screw the threaded bushing
into the filler block (left-hand thread). Because of the left-hand
and right-hand thread combination, the density monitor will move
into the threaded bushing simultaneously.
Tighten the threaded bushing to a torque of 30Nm.
After installation, there must be a gap (2 to 4mm) between the
collar of the threaded bushing and the filler block. The gap
ensures that the density monitor will rest securely on the filler
block.
Fill the vent hole (2a) in the threaded bushing with grease as per
L4.
In one equipment version, the switchgear is available with a den-
sity monitor unit of type EasyCheck.
The EasyCheck technology makes it particularly easy to perform
the emission-free density monitor test in correspondence with
the "F-gases regulation EU 517/2014" quickly and safely. (see
Chapter “12.1” on page 97)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE GL 313 F3/4031 P/VR and is the answer not in the manual?

GE GL 313 F3/4031 P/VR Specifications

General IconGeneral
BrandGE
ModelGL 313 F3/4031 P/VR
CategoryCircuit breakers
LanguageEnglish

Related product manuals