ADV200 • Quick start up guide 101
Signals for the digital outputs can be programmed using the Digital output 1...4
src parameters (13 - DIGITAL OUTPUTS menu, PAR: from 1310 to 1316) using
the settings in the L_DIGSEL1 selection list.
The drive also includes two analog outputs which are not factory-set. These
outputs must be enabled by setting Analog out 1 src (15 - ANALOG OUTPUTS
menu, PAR: 1800) and Analog out 2 src parameters (PAR: 1802) with a signal
selected from selection list L_ANOUT.
The signal available on analog output 1 is ± 10V, while the analog output 2 signal
can be selected using the Analog out 2 type parameter (PAR: 1848) between:
0 0-20mA
1 4-20mA
2 ± 10V
The analog output signal can be adjusted using Analog out 1 scale (PAR: 1808)
and Analog out 2 scale parameters (PAR:1810).
• Setting an analog output for reading a temperature sensor
1
2
3
4
Analog input 1
Analog input 2
Analog output 2
5
C1
0 V
6
S11
Analog output 1
The following is a description of the commissioning procedure to use the drive’s
ADV200 regulation card to acquire the temperature of a motor with KTY84 / PTC
sensors:
• The sensor can be powered via analog output 2 of the ADV200: connect the
signal to analog output 2 as shown (input 1 can be used as an alternative).
• Set analog output 2 to “current” via the Jumper (S3=I).
• Set analog output 2 (or 1) to voltage via the Jumper (S2=V or S1=V).
• On the ANALOG OUTPUTS menu, assign the value “0..20mA” to the Ana-
log out 2 type parameter (PAR 1848).
• On the ANALOG INPUTS menu, assign the value “-10V..+10V” to Analog
inp 2 type parameter (PAR 1552) or to the Analog inp 1 type parameter
(PAR 1502).
• On the ANALOG OUTPUTS menu, assign the selection “Null” to the Analog
out 2 src parameter (PAR 1802), which sets a null current in output.
• On the ANALOG INPUTS menu, run automatic calibration of the analog
offset of the selected output: 1 or 2 via the An inp 1 offset tune parameter
(PAR 1506) or the An inp 2 offset tune parameter (PAR 1556).
• On the ANALOG OUTPUTS menu, assign the selection “KTY84/PTC cur-
rent” to the Analog out 2 src parameter (PAR 1802), which lets you set a
current of 2mA in output to power the temperature sensor.
• On the ALARM CONFIG menu, assign the value “KTY84 An1” or “KTY84
An2” (“PTCAn1” or “PTC An2”), depending on the analog output selected,
to the MotorOT probe parameter (PAR 4530).
• On the MONITOR menu, the Motor temperature parameter (PAR 290)