ADV200 • Quick start up guide 101
Signals for the digital outputs can be programmed using the Digital output 1...4
src parameters (13 - DIGITAL OUTPUTS menu, PAR: from 1310 to 1316) using
the settings in the L_DIGSEL1 selection list.
The drive also includes two analog outputs which are not factory-set. These
outputs must be enabled by setting Analog out 1 src (15 - ANALOG OUTPUTS
menu, PAR: 1800) and Analog out 2 src parameters (PAR: 1802) with a signal
selected from selection list L_ANOUT.
The signal available on analog output 1 is ± 10V, while the analog output 2 signal
can be selected using the Analog out 2 type parameter (PAR: 1848) between:
0 0-20mA
1 4-20mA
2 ± 10V
The analog output signal can be adjusted using Analog out 1 scale (PAR: 1808)
and Analog out 2 scale parameters (PAR:1810).
• Setting an analog output for reading a temperature sensor
1
2
3
4
Analog input 1
Analog input 2
Analog output 2
5
C1
0 V
6
S11
Analog output 1
The following is a description of the commissioning procedure to use the drive’s
ADV200 regulation card to acquire the temperature of a motor with KTY84 / PTC
sensors:
The sensor can be powered via analog output 2 of the ADV200: connect the
signal to analog output 2 as shown (input 1 can be used as an alternative).
Set analog output 2 to “current” via the Jumper (S3=I).
Set analog output 2 (or 1) to voltage via the Jumper (S2=V or S1=V).
On the ANALOG OUTPUTS menu, assign the value “0..20mA” to the Ana-
log out 2 type parameter (PAR 1848).
On the ANALOG INPUTS menu, assign the value “-10V..+10V” to Analog
inp 2 type parameter (PAR 1552) or to the Analog inp 1 type parameter
(PAR 1502).
On the ANALOG OUTPUTS menu, assign the selection “Null” to the Analog
out 2 src parameter (PAR 1802), which sets a null current in output.
On the ANALOG INPUTS menu, run automatic calibration of the analog
offset of the selected output: 1 or 2 via the An inp 1 offset tune parameter
(PAR 1506) or the An inp 2 offset tune parameter (PAR 1556).
On the ANALOG OUTPUTS menu, assign the selection “KTY84/PTC cur-
rent” to the Analog out 2 src parameter (PAR 1802), which lets you set a
current of 2mA in output to power the temperature sensor.
On the ALARM CONFIG menu, assign the value “KTY84 An1” or “KTY84
An2” (“PTCAn1” or “PTC An2”), depending on the analog output selected,
to the MotorOT probe parameter (PAR 4530).
On the MONITOR menu, the Motor temperature parameter (PAR 290)