ADV200 • Quick start up guide 99
• Selecting the type of reference
After setting the regulation mode, the source of the speed reference must be set in
the Ramp ref 1 src parameter (05 REFERENCES menu, PAR: 610). This source
can be selected from among those listed in the L_MLTREF selection list:
1 Analog input 1 mon parameter (PAR: 1500) to use the signal applied to
terminals 1 – 2 of analog input 1 (14 - ANALOG INPUTS menu).
2 Dig ramp ref 1 parameter (05 - REFERENCES menu, PAR: 600) to set a
digital speed inside the drive.
3 Multi ref out mon parameter (07 - MULTI REFERENCE menu, PAR: 852) to
select the digital speeds using the digital inputs of the drive.
4 Mpot output mon parameter (08 - MOTOPOTENTIOMETER menu, PAR:
894) to use the internal motor potentiometer of the drive. If sending the com-
mand from the operator keypad, to use the motor potentiometer function enter
the Mpot setpoint parameter (PAR: 870) modify mode and press the Up (▲)
and Down (▼) keys.
5 Jog output mon parameter (09 - JOG FUNCTION menu, PAR: 920) to use
one of the drive’s internal jog speeds.
Signals from expansion cards, the serial line or eldbus can also be set as speed
references (see the detailed description of parameters).
• Setting the type of analog reference
If the analog input has been selected, choose the type of signal to use in the Ana-
log inp 1 type parameter (14 - ANALOG INPUTS menu, PAR.1502):
0 ± 10V
1 0-20mA o 0-10V
2 4-20mA
As well as programming the Analog inp 1 type parameter (PAR:1502) you must
also verify the position of the switches on the regulation card, as showed on
chapter 5.2.4.
• Ramps setting
The acceleration and deceleration ramps can be set in Acceleration time 0 (06 -
RAMPS menu, PAR: 700) and Deceleration time 0 (PAR: 702).
The signal available on the analog input can be adjusted using Analog inp 1
scale parameter (14 - ANALOG INPUTS menu, PAR: 1504), An inp 1 offset
tune parameter (PAR: 1506) and An inp 1 gain tune parameter (PAR: 1508).
To use a digital speed to control the drive, enter it in the Dig ramp ref 1 parameter
(05 - REFERENCES menu, PAR: 600).
The ramps are the same used with the reference signal from the analog input.
• Multispeed
To use more than one digital speed, use the multi-speed function.
First select the source of the speed signals Multi ref 0 src and Multi ref 1 src (07
- MULTI REFERENCE menu, PAR: 832 e 834) from the L_MLTREF selection list.
Next dene which digital inputs are to perform switching between the various
speeds; use the Multi ref sel .. src parameters (PAR: from 840 to 846) to select
the signals to use from the L_DIGSEL2 selection list. Set the desired speeds in
the Multi reference 0...7 parameters (PAR: from 800 to 814).