1.3. CONTROL TERMINALS
1
2
3
4
5
6
7
8
9
12
13
14
15
16
18
19
BU-
External braking
unit (optional)
Strip X1
Function
max
Programmable/configurable analog differential input. Signal: terminal 1.
Reference point: terminal 2. Default setting: Ramp ref 1
±10V
Programmable/configurable analog differential input. Signal: terminal 3. 0.25mA
Reference point: terminal 4. Default setting: none (20mA when
Programmable/configurable analog differential input. Signal: terminal 5.
current ref
input)
Reference point: terminal 6. Default setting: none. (1)
+10V
Reference voltage +10V; Reference point: terminal 9 +10V/10mA
-10V
Reference voltage -10V; Reference point: terminal 9 -10V/10mA
0V
Internal 0V and reference point for±10V -
Enable drive
Inverter enable; 0V or open: inverter disabled; +15…+30V: Inverte enabled
+30V
Start
Inverter start command; 0V or open: No start; +15…+30V: Start 3.2mA @ 15V
Fast stop
OV or open: Fast stop. +15…+30V: No Fast stop.
5mA @ 24V
External fault
OV or open: External fault. +15…+30V: No External fault
6.4mA @ 30V
COM D I/O
Reference point for digital inputs and outputs, term.12...15, 36...39, 41...42
-
0V24
Reference point for + 24V OUT supply, terminal 19 -
+24V OUT
+24V supply output. Reference point: terminal 18 or 27 or 28
+22…28V
120mA @ 24V
Analog input 1
Analog input 2
Analog input 3
Analog output
1
Program.analog output; def.setting: Motor speed. Ref. point: term.22
±10V/5mA
0V
Internal 0V and reference point for terminals 21 and 23
-
Analog output
2
Program.analog output; def.setting: Motor current. Ref. point: term.22
±10V/5mA
BU comm.
output
VeCon controlled BU-... braking units command. Ref. point: term.27.
+28V/15mA
0V24
Reference point for BU-... command, terminal 26
-
RESERVED -
Digital input 1 +30V
Digital input 2 3.2mA @ 15V
Digital input 3 5mA @ 24V
Digital input 4 6.4mA @ 30V
Digital output
1
+30V/40mA
Digital output
2
Supply D O
Supply input for digital outputs on terminals 41/42. Ref. point: term.16.
+30V/80mA
Motor PTC
1.5mA
Programmable digital output; default setting: none
Motor PTC sensing for overtemperature (cutoff R1k if used)
Programmable digital input; default setting: none
21
22
23
26
27
28
29
36
37
38
39
41
42
46
78
79
R1K
Strip X2
Function max curr.
250V AC
1AAC11
250V AC
1AAC11
OK relay
contact
Potential-relay contact configurable (relay 2).
Default: open 0 drive stopped
Relay 2
contact
Potential- relay contact OK relay (closed=OK)
80
82
83
85
RESERVED
Programmable digital input; default setting: none. Configurable as 1st encoder
index qualifier (”Digital input 4” parameter must be set 0=OFF ).
Progr. digital input; def. setting: none. Configurable as 2nd encoder index qualifier
(setting via S30 jumper, )”Digital input 3” parameter must be set 0=OFF

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran SIEIDrive AVy Series and is the answer not in the manual?

gefran SIEIDrive AVy Series Specifications

General IconGeneral
Brandgefran
ModelSIEIDrive AVy Series
CategoryController
LanguageEnglish

Related product manuals