5.11. DISCHARGE TIME OF THE DC-LINK
Table 5.11.1: DC Link Discharge Times
Type I
2N
Time (seconds) Type I
2N
Time (seconds)
1007 2.1
4300
58 60
1015 3.5
4370
76 90
1022 4.9
5450
90
1030 6.5
5550
110
2040 8.3
6750
142
2055 11
7900
180
2075 15.4
71100
210
3110 21.6
71320
250
3150 28.7
81600
310
4185 35,5 60
82000
365
120
4220
42 60
avy4250
120
90
150
205
220
This is the minimum time that must be elapsed since an AVy Drive is disconnected from the AC Input before
an operator may service parts inside the Drive to avoid electric shock hazard.
CONDITION These values consider a turn off for a Drive supplied at 480Vac +10%, without any option, ( the
charge for the switching supply is the regulation card, the keypad and the 24Vdc fans “if
mounted”).
The Drive is disabled. This represents the worst case condition.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran SIEIDrive AVy Series and is the answer not in the manual?

gefran SIEIDrive AVy Series Specifications

General IconGeneral
Brandgefran
ModelSIEIDrive AVy Series
CategoryController
LanguageEnglish

Related product manuals