——— Inspection procedure, component identification and standard specification ———
3.3. STANDARD SPECIFICATIONS
3.3.1. Permissible environmental conditions
Table 3.3.1.1: Environmental specification
[°C]
[°F]
Installation location
Installation altitude
Temperature:
operation
1)
operation
2)
storage
transport
Air humidity:
operation
storage
transport
Air pressure:
operation [kPa]
storage [kPa]
transport [kPa]
Climatic conditions
Clearance and creepage
Vibration
EMC compatibility
Approvals
T
A
Ambient temperature
E
N
V
I
R
O
N
M
E
N
T
IP54for the cabinet with externally mounted heatsink
(size type 100 7 to 3150)
IP20
Degree of protection
86 to 106 (class 3K3 as per EN50178)
86 to 106 (class 1K4 as per EN50178)
-25…+55°C (-13…+131°F), class 1K4 per EN50178
-20…+55°C (-4…+131°F), for devices with keypad
-25…+70°C (-13…+158°F), class 2K3 per EN50178
-20…+60°C (-4…+140°F), for devices with keypad
Up to 1000 m above sea level; for higher altitudes a current reduction of 1.2%
for every 100 m of
additional height applies .
0…40°C (32°…104°F)
0…50°C (32°…122°F)
0 …+40; +40…+50 with derating
32 …+104; +104…+122 with derating
Pollution degree 2 or better (free from direct sunligth, vibration, dust, corrosive
or inflammable gases, fog, vapour oil and dripped water, avoid saline
environment)
70 to 106 (class 2K3 as per EN50178)
IEC 68-2 Part 2 and 3
EN 50178, U L508C,UL840 degree of pollution 2
IEC68-2 Part 6
EN61800-3 (see “EMC Guidelines” instruction book)
CE, UL,cUL
avy2000
S
T
A
N
D
A
R
D
5% to 95 %, 1 g/m
3
to 29 g/m
3
(Class 1K3 as per EN50178)
5%to85%,1g/m
3
to 25 g/m
3
without moisture condensation or icing ( Class
3K3 as per EN50178)
95 %
3)
60 g/m
4)
A light condensation of moisture may occur for a short time occasionally if the device is
not in operation (class 2K3 as per EN50178)
1)
Parameter Ambient temp = 40°C (104°)
Ambient temp = 0 ... 40°C (32°...104°F)
Over 40°C: - current reduction of 2% of rated output current per K
- remove front plate (better than class 3K3 as per EN50178)
2)
Parameter Ambient temp = 50°C (122°F)
Ambient temp = 0 ... 50°C (32°...122°F)
Current derated to 0.8 rated ouput current
Over 40°C (104°): removal of the top cover (better than class 3K3 as per EN50178)
3)
Greatest relative air humidity occurs with the temperature @ 40°C (104°F) or if the temperature of the device is brought
suddenly from -25 ...+30°C (-13°...+86°F).
4)
Greatest absolute air humidity if the device is brought suddenly from 70...15°C (158°...59°F).