Model IFP-2100/ECS Installation Manual LS10143-001SK-E
9-1
Section 9
Programming
This section of the manual describes how to manually program the control panel from the built-in annunciator.
Each subsection discusses these menu options in detail. All options described in this section can be performed
using the HFSS - Honeywell Fire Software Suite.
9.1 UL 864 / UL 2572 Programming Requirements
Important!
Before any customized programming is done, JumpStart AutoProgramming should be run first. After
JumpStart is run, thoroughly test the system. The reason the system should be tested after JumpStart
AutoProgramming is because JumpStart AutoProgramming automatically programs the system, searching for
and configuring all SLC and SBUS devices it finds. JumpStart allows you to confirm the integrity of the
installation prior to performing any custom programming. After determining that the hardware is properly
installed, custom programming can be performed. Refer to Section 8.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES:
This product incorporates field programmable software. In order for the product to comply with the requirements in
the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, and Stand for Mass Notifications
Systems, UL 2572, certain programming features or options must be limited to specific values or not used at all as
indicated below.
Programming
Option
Menu Item
Permitted in
UL 864
(Y/N)
Permitted in
UL 2572
(Y/N)
Possible
Settings
Settings
Permitted in UL
864
Settings
Permitted in
UL 2572
Time Options Auto-resound Yes Yes 4 hrs, 24hrs 4 hours if using
SWIFT devices
4 hours if using
SWIFT devices
Time Options Low AC
Report Delay
Yes Yes 0–30 hours 1–3 1–3
Display Oldest
Event
Y (Enabled) Yes Yes Yes & No Yes Yes
N (Disabled) No No Yes & No No No
Initial Delay 0-28 Yes Yes 0-28 3 3
Inter Message Delay 4-32 Yes Yes 4-32 4-32 4-28
Alarm Verification Alarm
Verification
Yes Yes 60-250
(confirmation
period)
60 60
Auto Reset ECS
MIC Triggered Event
Auto Reset
ECS Custom
Event
Yes Yes Never
Timer Event
Disabled
Never
Timer Event
Disabled
Never
Timer Event
Disabled
ECS Input ECS Input Yes Yes Latching
Non-Latching
Latching Latching
Event Priority CO Alarm No No Yes & No No No

Table of Contents

Other manuals for Honeywell ECS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ECS Series and is the answer not in the manual?

Honeywell ECS Series Specifications

General IconGeneral
BrandHoneywell
ModelECS Series
CategoryConference System
LanguageEnglish

Related product manuals