Model IFP-2100/ECS Installation Manual LS10143-001SK-E
4-3
4.3 Battery Power
The batteries must be sealed lead acid type. Before connecting the batteries to the FACP, make certain that the
interconnect cable between the batteries is not
connected. Do not connect the battery jumper cable until the
system is completely installed. Observe polarity when connecting the batteries.
The control panel battery charge capacity is 17 to 55 AH. Use 12V batteries of the same AH rating. Determine
the correct AH rating as per your standby load calculation (see Section 3.7).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating. It is
recommended that you replace batteries every five years.
Figure 4-4 Battery Connection
4.3.1 Battery Accessory Cabinets
The Model RBB or AB-55 Accessory cabinets can be used when you are required to use backup batteries that are
too large to fit into the main control panel cabinet.
The RBB cabinet holds batteries up to the 35 AH size. The RBB dimensions are 16" W x 10" H x 6" D (40.64 cm
W x 25.4 cm H x 15.24 cm D).
The AB-55 Accessory cabinet holds batteries up to the 55AH size. The AB-55 dimensions are 20" W x 11.5" H x
7.5" D (50.8 cm W x 30.48 cm H x 19.05 cm D).
4.3.1.1 Installing the RBB or AB-55 Accessory Cabinet and
Batteries
To properly install the accessory cabinet and backup batteries, follow these steps:
1. Mount the accessory cabinet. See Figure 4-5 for the four cabinet mounting holes.
• If mounting onto drywall the accessory cabinet must be mounted onto ¾-inch ply-
wood. This is necessary because the weight of the batteries inside the accessory cabi-
net could cause the cabinet to pull away from the drywall.
• When mounting on concrete, especially when moisture is expected, attach a piece of
WARNING: RISK OF PERSONAL INJURY
Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If
contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek
immediate medical attention
Red
Black
Battery Jumper
(P/N 140694)
Shipped With Panel