LS10143-001SK-E System Operation
10-10
The Event Priority Table contains the following events for modification:
Note: Status Points, Status Voice Aux 1, Status Voice Aux 2, and Background Music are contained within the Sys-
tem Status event priority.
Note: All fire, emergency and system troubles are prioritized into the Trouble event priority.
10.5.4 Priority Rules
1. Event priorities can be changed only within, not between, priority levels (defined by bold lines in Table 10-
1).
2. Emergency LOC Alarm must always higher than Emergency 1-8 Point Alarm and Emergency Voice Aux 1-
4 Alarm.
3. ECS events do not need to be in order by ECS number.
10.5.5 Other Priority Considerations
There are other considerations to take into account when the same event is acting on the same output group (an
event being mapped to an output group.) These are prioritized in order of appearance:
For voice system utilizing dual channel, normal mapping takes priority over alert mapping. Example: Zone 1
Manual Pull is mapped to Voice Group 1 as an Alert 1 mapping and Zone 2 Manual Pull is mapped to Voice
Group 1 as a normal mapping. If Zone 1 and Zone 2 Manual Pull events are active, Voice Group 1 will
annunciate the Fire Alarm message defined in the Voice Settings for the panel's assigned site.
Event priority is considered here based on the Event Priority Table.
If an output group is mapped both directly and through an output group template to an event, the direct map
Table 10-1: Event Priority Table
Fire System Emergency System
Fire Manual Pull Alarm Emergency LOC Alarm
Fire Detector Alarm Emergency 1 Point Alarm
Fire Water Flow Alarm Emergency 2 Point Alarm
Fire Interlock Release Alarm Emergency 3 Point Alarm
Fire Zone Aux 1 Alarm Emergency 4 Point Alarm
Fire Zone Aux 2 Alarm Emergency 5 Point Alarm
Fire System Aux 1 Alarm Emergency 6 Point Alarm
Fire System Aux 2 Alarm Emergency 7 Point Alarm
Emergency 8 Point Alarm
Emergency Voice Aux 1 Alarm
Emergency Voice Aux 2 Alarm
Emergency Voice Aux 3 Alarm
Emergency Voice Aux 4 Alarm
CO Alarm
Fire Pre-Alarm
Fire Interlock Alert
Emergency Supervisory
Fire Supervisory
CO Supervisory
Trouble
Site F Key Status
System Status

Table of Contents

Other manuals for Honeywell ECS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ECS Series and is the answer not in the manual?

Honeywell ECS Series Specifications

General IconGeneral
BrandHoneywell
ModelECS Series
CategoryConference System
LanguageEnglish

Related product manuals