Model IFP-2100/ECS Installation Manual LS10143-001SK-E
1
Appendix A
Compatible Devices
A.1 Notification Appliances
For proper operation, you must use polarized devices with a model 7628 4.7k ohm EOL resistor on each loop.
All supervised notification appliances used with the control panel must be polarized.
Note: Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the devices you have chosen
will work with this feature. This control is UL listed for panel wide Synchronization.
Table A-1 below lists notification appliances compatible with the fire alarm control panel. Appliances which can
be synchronized indicate the type of SYNC available in the columns marked Audio and Visual
.
Table A-1 Compatible Notification Appliances
Manufacturer Model Audio Visual Type
AMSECO
SH24W-153075
X
X Horn/Strobe
SAD24-153075 X Strobe
SAD24-75110 X Strobe
SL24W-75110 X Strobe
SL24C-3075110 X Strobe
SLB24-75 X Strobe
RSD24-153075 X Strobe
RSD24-75110 X Strobe
SH24W-75110 X X Horn/Strobe
SH24W-3075110 X X Horn/Strobe
SHB24-75 X X Horn/Strobe
SCM24W-153075 X X Chimes/Strobe
SCM24W-75110 X X Chimes/Strobe
SCM24C-3075110 X X Chimes/Strobe
SCM24C-177 X X Chimes/Strobe
H24W X Horn
H24R X Horn
FCI
S2415-FC X Strobe
S241575-FC X Strobe
S2430-FC X Strobe
130-3117C X Mini Horn
130-3147C X Mini Horn
BLV-6 X Vibrating Bell
BLV-10 X Vibrating Bell
BLVCH X Vibrating Chime
H12/24-FC X Horn
H12/24W-FC X Horn