EasyManuals Logo
Home>Honeywell>Conference System>ECS Series

Honeywell ECS Series User Manual

Honeywell ECS Series
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #78 background imageLoading...
Page #78 background image
LS10143-001SK-E Control Panel Installation
4-36
2. Configure the circuit through programming (see Section 9.5).
Figure 4-49 Class B Input Switches
4.15.2.2 Class A Inputs
You can connect conventional Class A switches, such as waterflow switches and pull stations, directly to the
Flexput circuits of the control panel.
To install a Class A switch:
1. Wire the Class A switch as shown in Figure 4-50.
2. Configure the circuit through programming (see Section 9.5).
Figure 4-50 Class A initiating Switches
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-50 uses both Flexput circuit 1 and 2, so in programming it
would be referred to as point 1.
4.15.3 Installing 2-Wire Smoke Detectors
Any compatible UL listed two-wire smoke detector can be used with the control panel (see Appendix A for list
of compatible smoke detectors). Figure 4-51 and Figure 4-52 illustrate how to connect a UL listed 2-wire
detector to the control panel.
supervised
Maximum Impedance
per circuit is 50
Ω
power limited
EOL 4.7 kΩ
Note:
Flexput circuit 1 and 2
used as an example.
Any Flexput point pairing
could be used.
supervised
power limited
Maximum Impedance per circuit is 50Ω

Table of Contents

Other manuals for Honeywell ECS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ECS Series and is the answer not in the manual?

Honeywell ECS Series Specifications

General IconGeneral
BrandHoneywell
ModelECS Series
CategoryConference System
LanguageEnglish

Related product manuals