LS10143-001SK-E Reporting
12-14
2. Multiple events can be sent within a single event block. Events are separated by a “/” character.
3. Event parameter can be either a zone, point or module number.
4. When reporting by point is enabled, the communicator uses a “pi” event to supersedes the actual point event
to report the module the point is linked to.
5. Panel ID is not sent in the SIA event parameters.
For Example see Table 12-3:
12.3 SIA – IFP-2100/ECS Panel Communicator:
(Differences/additional features are underlined)
Events are sent to the Central Station Receiver as a fixed length string:
The event format is:
EEPPMMZZZZ
Where
EE Event code (2 characters)
PP Panel number (2 digits – Zero Filled) (valid range from 1 to 64)
MM Module number (2 digits – Zero Filled) (valid range from 1 to 98, typically
Table 12-3: SIA- IntelliKnight / IFP-2100/ECS Panels - PI Modifier Reporting Examples
Event
Report
Zone/ Point
Panel ID
Module
Zone ZZZZ
Point
ZZZZ
Fields Sent
SIA Event
Data
Fire Alarm-Zone Zone n/a n/a97 15 n/a EE-ZZ FA15
Fire Alarm-Zone Zone n/a n/a 05 n/a EE-Z FA5
Fire Alarm-Point Point n/a 01 n/a 123 EE-ZZ /EE-
ZZZ
pi01/FA123
Fire Alarm-Point Point n/a 33 n/a 203 EE-ZZ /EE-
ZZZ
pi11/FA203
Expander Trouble n/a n/a 11 n/a n/a EE-ZZ ET11
Auto Test n/a n/a n/a n/a n/a EE-Z RP0
Battery Trouble-Panel 32 n/a n/a 98 n/a n/a EE-ZZ YT98
Battery Trouble-Expander
18
n/a n/a 18 n/a n/a EE-ZZ YT18
SLC Loop Shorted n/a n/a 44 n/a n/a EE-ZZ ET44
Program Begin Panel
ID=32
n/a n/a n/a n/a n/a EE-Z LB0
Program Begin Panel ID=
22
n/a n/a n/a n/a n/a EE-Z LB0
AC Power Loss - Panel 22 n/a n/a 98 n/a n/a EE-Z AT0
Fire Trouble Point n/a 97 n/a 200 EE-ZZ /EE-
ZZZ
pi97/FT200
Fire Trouble Zone n/a 97 01 n/a EE-Z FT1
Fire Trouble-Nac Point n/a 98 n/a Nac
Circuit 7
EE-ZZ /EE-
Z
pi98/FT7
Z=Pt. #
Fire Trouble-Nac Zone n/a 98 n/a Nac
Circuit 7
EE-ZZZ FT400
ZZZ=OPG#