Model IFP-2100/ECS Installation Manual LS10143-001SK-E
12-15
Module information)
ZZZZ Event parameter (4 digits – Zero Filled) (typically Point, Zone or Circuit
information)
1. The Event field will contain 10 digits including the 2 digit event code (EE), 2 digit panel ID (PP), 2 digit
Module Number (MM) and a 4 digit Event Parameter (ZZZZ).
2. Based on the actual Event Code, the Module Number or Event Parameter fields might not contain pertinent
information. In that case the field will contain zeros.
3. The account number is sent using an account block that is separate from the event block.
4. Multiple events can be sent within a single event block. Events are separated by a “/” character.
5. Event parameter can be a Zone, Point or Circuit Number.
6. “pi” modifier event is not used.
7. Panel can be set to report by either Point or Zone.
For examples see Table 12-4.
Table 12-4: IFP-2100/ECS SIA REPORTING EXAMPLES
Event
Report
Zone/
Point
Panel ID
PP
Module
MM
Zone
ZZZZ
Point
ZZZZ
Fields
Sent
SIA Event
Data
Fire Alarm-Zone Zone 32 n/a 15 n/a EE-PP-MM-ZZZZ FA32000015
Fire Alarm-Zone Zone 32 n/a 05 n/a EE-PP-MM-ZZZZ FA32000005
Fire Alarm-Point Point 32 01 n/a 123 EE-PP-MM-ZZZZ FA32010123
Fire Alarm-Point Point 21 33 n/a 203 EE-PP-MM-ZZZZ FA21330203
Expander Trouble n/a 15 11 n/a n/a EE-PP-MM-ZZZZ ET15110000
Auto Test n/a 32 n/a n/a n/a EE-PP-MM-ZZZZ RP32000000
Battery Trouble-Panel 32 n/a 32 98 n/a n/a EE-PP-MM-ZZZZ YT32980000
Battery Trouble-Expander 18 n/a 32 18 n/a n/a EE-PP-MM-ZZZZ YT32180000
SLC Loop Shorted n/a 01 44 n/a n/a EE-PP-MM-ZZZZ ET01440000
Program Begin n/a 32 n/a n/a n/a EE-PP-MM-ZZZZ LB32000000
Program Begin n/a 22 n/a n/a n/a EE-PP-MM-ZZZZ LB22000000
AC Power Loss- Panel 22 n/a 22 98 n/a n/a EE-PP-MM-ZZZZ AT22980000
MM = 00
Fire Trouble Point 22 97 n/a 200 EE-PP-MM-ZZZZ FT22970200
Fire Trouble Zone 22 97 1 n/a EE-PP-MM-ZZZZ FT22970001
MM = 00
Fire Trouble-Nac Point 22 98 n/a Nac Circuit 7 EE-PP-MM-ZZZZ FT22980007
ZZZZ=Pt. #
Fire Trouble-Nac Zone 22 98 n/a Nac Circuit 7 EE-PP-MM-ZZZZ FT22980007
ZZZZ=OPG #

Table of Contents

Other manuals for Honeywell ECS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ECS Series and is the answer not in the manual?

Honeywell ECS Series Specifications

General IconGeneral
BrandHoneywell
ModelECS Series
CategoryConference System
LanguageEnglish

Related product manuals