LS10143-001SK-E Programming
9-12
9.5.2 Point Programming For 6815 Module
To program for points on an 6815 module, follow these steps:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select 7 for Panel Programming.
3. Press 4 to enter point menu.
4. Press the up or down arrow key to select the desired module. Refer to Section 8.5 Quick Reference Table for
available choices. Then press ENTER.
5. Select S for sensor or M for module. (IDP or SK Only)
6. Enter the number of the point you wish to edit, then press ENTER.
7. Select the type of device by pressing the up or down arrow key. Refer to Table 9-5 under the column heading
“Type Selection” for a list of choices.
RELAY
OUTPUT PT Select Group Output point, a general use relay type. Use for applications requiring
a relay, such as fan shutdown, elevator recall, and so on.
AUX RESET Use for auxiliary power, resettable applications. See Section 4.15.5
for a description of how this option operates.
AUX DOOR Use for auxiliary power, door holder applications. For example, if
you were using an auxiliary power supply for door holders, you
would use this option. See Section 4.15.5.1 for a description of how
this option operates.
SLC LED
LED NUMBER 01-80 For use with SD devices only. 80 sub addresses on LED.
LED FUNCTION Unused
NOTIF Notification can have group number.
Table 9-5: Programming Options for 6815 Modules
Type
Selection
Function Latching Option Comments
UNUSED Select for SLC points that are unused.
DETECTOR
PHOTO Spot photoelectric detectors.
ION Spot ION detectors
HEAT Spot heat detector.
PHOTO DUCT Duct photoelectric detector.
ACCLIMATE Acclimate photoelectric detector.
HEAT HT High temperature heat detector.
PHOTO-HEAT Photoelectric detector with heat sensor.
BEAM Beam smoke detector.
Table 9-4: Programming Options for 5815XL Modules
Type
Selection
Function Latching Option Comments

Table of Contents

Other manuals for Honeywell ECS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ECS Series and is the answer not in the manual?

Honeywell ECS Series Specifications

General IconGeneral
BrandHoneywell
ModelECS Series
CategoryConference System
LanguageEnglish

Related product manuals