Model IFP-2100/ECS Installation Manual LS10143-001SK-E
2-3
P.A.S. (positive alarm sequence) feature shall be used only with automatic detectors.
2.2.2 Requirements for Central Station Fire Alarm Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the IFP-2100/ECS shall automatically initiate and
complete a test signal transmission sequence to its associated receiver at least once every 6 hrs.
3. The AC Loss Hours option must be set from 1-3 hours.
4. If using wired Ethernet or cellular, you must program the corresponding account/subscriber ID and a test
time so that the FACP shall automatically initiate a test signal transmission sequence to its associated
receiver at least once every 6hrs.
2.2.3 Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used.
2.2.4 Requirements for Remote Station Protected Fire Alarm
Systems
Minimum system requirements are one Honeywell Silent Knight addressable initiating device and wither a 5220,
Keltron 3158 or the built-in Digital Alarm Communicator Transmitter (DACT).
1. Do not exceed the current draw load restrictions shown in Section 3.7.
2. The AC Loss Hours option must be set from 1-3 hours.
2.2.5 Requirements for the Installation of Carbon Monoxide (CO)
Detection and Warning Equipment, NFPA 720
When using carbon monoxide detection the system must be monitored by a Supervising Station.
2.2.6 NFPA Requirements
The following is the minimum configuration to meet the NFPA requirements.
Table 2-1 NFPA Requirements for IFP-2100 or RFP-2100
Model/
Module
Description Local Releasing Auxiliary
Remote
Station
Central
Station
021000 Motherboard YYYYY
RFP-2100 Remote unit O (1) O (1) O (1) O (1) O (1)
Cell-ModTransmitterOOOOO
5220 Rev Pol Mod O O Y Y O
5815XL SLC Exp OOOOO
5824 Serial card OOOOO
7644 Rev pol mod O O N Y O
6815 SLC Exp OOOOO
SK-NICNetwork cardOOOOO
SK-FMLFiber moduleOOOOO

Table of Contents

Other manuals for Honeywell ECS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ECS Series and is the answer not in the manual?

Honeywell ECS Series Specifications

General IconGeneral
BrandHoneywell
ModelECS Series
CategoryConference System
LanguageEnglish

Related product manuals