3.4 Electrical Specifications
Table 3-1 list the terminal block on the IFP-2100/ECS as well as a description of each individual terminal and
their respective electrical rating.
Table 3-1 Terminal Descriptions and Electrical Specifications
Terminal Label Description Rating
Earth Ground
Faults
Voltage Current
B
AC input (hot) 120/240 VAC
50/60 Hz
4.5A for the IFP-2100
2.8A for the IFP-2100HV
N/A
G Earth ground N/A N/A N/A
W
AC input (neutral) 120/240 VAC
50/60 Hz
4.5A for the IFP-2100
2.8A for the IFP-2100HV
N/A
X
*I/O 1
Flexput™ Circuits 24 VDC 3.0 A notification and
auxiliary power circuits
0Ω
O 100 mA for initiation circuits
X
*I/O 2
Flexput™ Circuits 24 VDC 3.0 A notification and
auxiliary power circuits
0Ω
O 100 mA for initiation circuits
X
*I/O 3
Flexput™ Circuits 24 VDC 3.0 A notification and
auxiliary power circuits
0Ω
O 100 mA for initiation circuits
X
*I/O 4
Flexput™ Circuits 24 VDC 3.0 A notification and
auxiliary power circuits
0Ω
O 100 mA for initiation circuits
X
*I/O 5
Flexput™ Circuits 24 VDC 3.0 A notification and
auxiliary power circuits
0Ω
O 100 mA for initiation circuits
X
*I/O 6
Flexput™ Circuits 24 VDC 3.0 A notification and
auxiliary power circuits
0Ω
O 100 mA for initiation circuits
X
*I/O 7
Flexput™ Circuits 24 VDC 3.0 A notification and
auxiliary power circuits
0Ω
O 100 mA for initiation circuits
X
*I/O 8
Flexput™ Circuits 24 VDC 3.0 A notification and
auxiliary power circuits
0Ω
O 100 mA for initiation circuits
B
SBUS1 OUT
SBUS communication 5 VDC 100 mA 0Ω
A
+ SBUS power 24 VDC 1.0 A
-
B
SBUS1 IN
Used for Class A installations 0Ω
A
+
-
* Regulated for NAC circuits, special application when used for releasing or auxiliary power circuits.