Model IFP-2100/ECS Installation Manual LS10143-001SK-E
3-19
3.7.5 Maximum Battery Standby Load
Table 3-5 and Table 3-6 show the standby load calculations for the IFP-2100 based on 24 and 90 hours of
standby. The standby load calculations of line D in the Current Draw Calculation Worksheet must be less than
the number shown in Table 3-5 and Table 3-6 for the selected battery size, standby hour and alarm time. The
numbers below have a built in 20% derating factor for the battery amp-hour capacity.
*For FM Installation only
Table 3-5: Maximum Battery Standby Loads for 24 Hour Standby
Rechargeable
Battery Size
24 hr Standby,
5 mins. Alarm
24 hr Standby,
15 min alarm
24 hr Standby,
20 min alarm
17AH 535 mA 473 mA 442 mA
18AH 569 mA 506 mA 475 mA
24AH 769 mA 706 mA 675 mA
33AH 1.07A 1.01A 975 mA
35AH 1.14A 1.07A 1.04A
40AH 1.30A 1.24A 1.21A
55AH 1.80A 1.74A 1.71A
Table 3-6: Maximum Battery Standby Loads for 90 Hour Standby*
Rechargeable
Battery Size
90 hr Standby,
5 min alarm
90 hr Standby,
15 min alarm
90 hr Standby,
20 min alarm
33 AH N/A N/A N/A
40 AH 347 mA 331 mA 322 mA
55 AH 480 mA 464 mA 456 mA
Warning
Honeywell Silent Knight does not support the use of batteries smaller than those listed in Table 3-5 and Table 3-6. If you
use a battery too small for the installation, the system could overload the battery resulting in the installation having less
than the required 24 hours standby power. Use Table 3-5 and Table 3-6 to calculate the correct battery amp hour rating
needed for your installation. It is recommended that you replace batteries every five years.