LS10143-001SK-E Control Panel Installation
4-4
¾-inch plywood to the concrete surface and then attach the RBB or AB-55 cabinet to
the plywood.
• If using the battery cable extenders provided (P/N 140643), mount the RBB or AB-55
cabinet no more than 18" away from the main control panel cabinet. This will ensure
that the battery cables reach the battery terminals.
Figure 4-5 RBB or AB-55 Cabinet Mounting Holes
2. Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4-6.