EXCEL CARE CONTROL ICONS ALPHABETIC REFERENCE
111 74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
The following table lists parameters used for the automatic switch-on of load after
maximum OFF time has expired:
Parameter
Number
Type
Description
Setting
Range
Default
Value
Unit
5
Display
Minimum ON Time Active
none
none
Integer
7
Display
Maximum OFF Time Expired
none
none
Integer
10
Comm.
Minimum ON Time
0-300
60
sec
12
Comm.
Maximum OFF Time
0=No maximum OFF time
function
0-1440
15
min
RM Functions
Parameter P16 determines whether the RM input of XFM 36-1/S/R provides load
status feedback, is an additional control to switch on the load, or has no effect at all.
If Parameter P16 is 0, XFM 36-1/S/R uses the RM input to receive the status
feedback (ON or OFF) from the load. The input RM initiates the minimum ON or
OFF time functions when load status changes from OFF to ON or from ON to OFF,
respectively .
If Parameter P16 is 1, XFM 36-1/S/R uses the input RM as a software input for
additional load control by another software module. The command (ON or OFF) to
the load in the result of Boolean ANDing of the command of the regular XFM 36-
1/S/R functions as influenced by the Po input value AND the state of the RM input.
XFM 36-1/S/R transfers this switching result (ON/OFF) to the second output St after
minimum ON or OFF time elapses.
If Parameter P16 is 2 (default setting), input RM has no function. Connect the RM
input to a dummy digital flag to ensure all XFM 36-1/S/R I/Os are connected.
Display Parameter P3 indicates the current status of the second input, RM. A 1
value indicates that RM is ON; a 0 indicates that RM is OFF.
The following table lists the parameters used for the second input RM functions:
Parameter
Number
Type
Description
Setting
Range
Default
Value
Unit
3
Display
RM Input State
none
none
Integer
16
Progr.
Feedback _Op_Mode
0=RM for status feedback
1=RM AND Po
2=No RM function
0/1/2
2
Integer
XFM 36-1 General Functions
XFM 36-1/S/R includes general functions to provide a manual operating mode,
stability, special features, and alarm indications. These functions have a high priority
in making the final decisions about load switching.

Table of Contents

Other manuals for Honeywell EXCEL 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell EXCEL 5000 and is the answer not in the manual?

Honeywell EXCEL 5000 Specifications

General IconGeneral
BrandHoneywell
ModelEXCEL 5000
CategoryControl Systems
LanguageEnglish

Related product manuals