ALPHABETIC REFERENCE EXCEL CARE CONTROL ICONS
74-5577–33 (US) 44
EN2B-0184 GE51 R0518 (Europe)
Decimal Places (Excel Web / Excel Web II)
Function Returns the value of the decimal places part of the input value (X=3.175 becomes
Y=0.175)
I/O Dialog Box
Input One analog input (X).
Output One analog output (Y).
Internal Parameters None.
Delay (Excel Web / Excel Web II)
Function “Switch-on” delay.
I/O Dialog Box
Inputs Two digital inputs (A and B)
Outputs Two digital outputs where:
Y will become value of A after delay time:
If A < 1, then Y = 0
If A >= 1, then Y = 1 (after delay time)
If A < 1 within delay time, delay time is reset
Alarm indicates a difference between the two inputs:
If Y = 1 and input B < 1, then alarm signal = TRUE (1),
Internal Parameter
Parameter Description
P1 Delay time with 10 sec value and a limit of 0<=x.