EasyManuals Logo
Home>Honeywell>Control Systems>EXCEL 5000

Honeywell EXCEL 5000 User Manual

Honeywell EXCEL 5000
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #226 background imageLoading...
Page #226 background image
ALPHABETIC REFERENCE EXCEL CARE CONTROL ICONS
74-5577–33 (US) 228
EN2B-0184 GE51 R0518 (Europe)
Time Counter (Excel Web / Excel Web II)
Function Counts the runtime when the input signal X is greater than or equal to 1. If the
counter reset signal Rst
is greater than or equal to 1, the runtime is reset to 0.
I/O Dialog Box
Inputs Two inputs where:
X = input signal (>= 1 start counting runtime)
Rst = reset signal (>= 1 reset runtime to 0)
Outputs Two outputs where:
Hr on = runtime in hours
Min on = runtime in minutes
Internal Parameters None.
Timer Value (Excel Web / Excel Web II)
Function Legacy RACL function "RTIM": Counts the time in seconds. Can be reset by the
"Reset Timer" function.
I/O Dialog Box
Outputs One analog output (T). Timer value in sec.
Internal Parameters None.
Truncate (Excel Web / Excel Web II)
Function Truncates the decimal places, e.g. 3.1 becomes 3, -3.1 becomes -3)
I/O Dialog Box
Input One analog input (X).
Output One analog output (Y).
Internal Parameters None.

Table of Contents

Other manuals for Honeywell EXCEL 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell EXCEL 5000 and is the answer not in the manual?

Honeywell EXCEL 5000 Specifications

General IconGeneral
BrandHoneywell
ModelEXCEL 5000
CategoryControl Systems
LanguageEnglish

Related product manuals