EXCEL CARE CONTROL ICONS
276 74-5577–31 (US)
EN2B-0184 GE51 R0516 Europe)
APPENDIX B: STARTUP USER ADDRESS
Definition The STARTUP user address (or “point”) is a digital pseudopoint that the controller
sets to zero when power to the controller is off. Power-off can occur because of a
restart or a power failure. When power returns, the controller sets STARTUP to 1.
This set occurs before the controller application program starts.
You can define special start-up procedures after a power failure or download by
resetting STARTUP to zero after a complete program cycle has run.
You can use a switching table to set STARTUP and provide the start-up action
shown in the following diagram.