EXCEL CARE CONTROL ICONS ALPHABETIC REFERENCE
35 74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
CHA Example Control operating hours for two continually controller pumps. You can alternate
between two pumps as the following diagram shows:
The application programs for speed control and pump switching are control loops
with one or more switching tables.
Compare 2 (Excel Web II)
Prerequisite Controller OS 3.01.00 or higher
Function Compares two analog inputs (A and B).
Formula The outputs are set according to the comparisons "A >= B" and "A <= B" to 1 if the
result is true and 0 if the result is false.
I/O Dialog Box
Input Two analog inputs (A and B)
A = First input value
B = Second input value
Output Two analog outputs where:
A >= B: result of comparison A >= B
A <= B: result of comparison A <= B
Internal Parameters None
Registers None
Comparison (Excel Web / Excel Web II)
Function Compares input A and B.