ALPHABETIC REFERENCE EXCEL CARE CONTROL ICONS
74-5577–33 (US) 22
EN2B-0184 GE51 R0518 (Europe)
Absolute (Excel Web / Excel Web II)
Function Returns the absolute value and the algebraic sign of an analog value.
I/O Dialog Box
Input One analog input.
Output One analog output (Abs = Absolute value of input)
One digital output (Sign = sign (TRUE(1) if input is negative).
Internal Parameters None.
Addition / ADD
Function Sum multiple analog input values.
I/O Dialog Box
Excel Web / Excel Web II
Inputs Two through six analog inputs (X1 through X6).
You can enter the first input as a parameter (engineering unit index number and
value).
Two through thirty two analog inputs (1 through 32, Excel Web / Excel Web II).
Output One analog output (Y).