EXCEL CARE CONTROL ICONS ALPHABETIC REFERENCE
31 74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
Cascade Plus / CAS
Function Cascade controller that acts as a PI controller with a master and cascade controller.
Cascade Differences This cascade controller (CAS Plus) acts just like the previous cascade controller
except that it has an integral action enable/disable input. This new function requires
an additional digital input (XD) and two new parameter registers for temporary
storage.
This additional input enables CAS Plus to act as a P controller during plant start-up
and then switch on an Integral component after start-up is complete.
I/O Dialog Box
Excel Web / Excel Web II
Inputs Three analog inputs, where:
X = Master-controlled variable.
XH = Cascade- or auxiliary-controlled variable.
W = Reference variable, also known as setpoint
You can enter the reference variable as a parameter (engineering unit index number
and value). Not for Excel Web / Excel Web II !
One digital input (XD, Excel Web / Excel Web II Icon) that enables and disables
integral control action. When XD is zero, integral action in the master and cascade
controllers is disabled and the associated integral sum is reset. XD/Ion must always
be connected.
Outputs One analog output (Y).

Table of Contents

Other manuals for Honeywell EXCEL 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell EXCEL 5000 and is the answer not in the manual?

Honeywell EXCEL 5000 Specifications

General IconGeneral
BrandHoneywell
ModelEXCEL 5000
CategoryControl Systems
LanguageEnglish

Related product manuals