EasyManuals Logo
Home>Honeywell>Transmitter>XNX

Honeywell XNX Technical Manual

Honeywell XNX
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #110 background imageLoading...
Page #110 background image
XNX Universal Transmitter
Section 5 - Warnings/Faults
108
5.1 Warning Messages
Warning Description
Applicable
Sensors
Latching / Non-Latching
Frequency of Diag-
nostic
Event History Data Action For Resolution
W001
XNX
®
24VDC
SupplyBad
All Non-latching 2seconds
XNXsupply
voltagex1000
Checkwireof24VpowersupplytoXNXaswellaspowersupplyopera-
tion�
W002
XNXTempera-
tureError
All Non-latching 2seconds
XNXtempera-
ture(Celsius)
Checklocationforheatsources�Fitwithsunshadeorotherprotection�
ChangelocationofXNX�ChecktemperatureinInfo->TransmitterStatus
toensuretemperatureisbeingmeasuredproperly
W003
Simulated
Warning/Fault
All Non-latching Enabledbyuser 0 Performinganalarm/faultresetwillclearallsimulation�
W005
SensorTem-
peratureError
Optima Non-latching
XNXpollssensor
every2seconds,
diagnosticfre-
quencycontrolled
bysensor
Sensorfaultor
warningcode
(Note4)
Checklocationforheatsources�Fitwithsunshadeorotherprotection�
ChangelocationofXNX�ChecktemperatureinInfo->SensorStatusto
ensuretemperatureisbeingmeasuredproperly
SensorTem-
peratureError
Excel Non-latching
XNXpollssensor
every2seconds,
diagnosticfre-
quencycontrolled
bysensor
Sensorfaultor
warningcode
(Note4)
Checklocationforheatsources�Fitwithsunshadeorotherprotection�
ChangelocationofXNX�ChecktemperatureinInfo->SensorStatusto
ensuretemperatureisbeingmeasuredproperly
SensorTem-
peratureError
ECC Non-latching 2seconds
Sensortemper-
ature(Celsius)
Checklocationforheatsources�Fitwithsunshadeorotherprotection�
ChangelocationofXNX�ChecktemperatureinInfo->SensorStatusto
ensuretemperatureisbeingmeasuredproperly
W006
NegativeDrift ECC,mV Non-latching 2seconds
Rawgascon-
centrationof
sensor
Checksensorlocationforexternalinterference�Performzerocalibra-
tion�Ifproblempersistsafterzerocalibrationandnointerferenceexists,
replacesensor
NegativeDrift
Optima,
Excel
Non-latching
XNXpollssensor
every2seconds,
diagnosticfre-
quencycontrolled
bysensor
Sensorfaultor
warningcode
Checksensorlocationforexternalinterference�Performzerocalibra-
tion�Ifproblempersistsafterzerocalibrationandnointerferenceexists,
replacesensor
W007
Calibration
Required
All Non-latching 2seconds
Numberofdays
remaininguntil
calibrationex-
pires,negative
=numberof
daysexpired
Timesincethelastspancalibrationhasexceededadenedlimit�Per-
formingasuccessfulspancalibrationwillclearthecondition�Thelimitis
theuser-denedcalibrationinterval�W007canbedisabledbysettingthe
calibrationintervalto0�

Table of Contents

Other manuals for Honeywell XNX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX and is the answer not in the manual?

Honeywell XNX Specifications

General IconGeneral
BrandHoneywell
ModelXNX
CategoryTransmitter
LanguageEnglish

Related product manuals