62
Para
metre
Setting
Set
value Description/Setting range
P001P001
System type 0
0 = Xclusive Combination
1 = Xclusive System boiler + cylinder
2 = Xclusive Instantaneous water heater
3 = Xclusive System boiler
P010P010
Set maximum central heating output
75
-------
100
75 = Xclusive 36
100 = Xclusive 24 / Xclusive 30
25% to 100% (see §9.5)
P030P030
Central heating pump setting 0
0 = overrun active
1 = continuous
1
P031P031
Maximum capacity of modulating central
heating pump
65 Value displayed as a percentage (%)
P032P032
Minimum capacity of modulating central
heating pump
35 Set 15% of parameter P031
P033P033
Central heating pump overrun aer central
heating demand
1 0 to 15 minutes
P034P034
Central heating pump overrun aer boiler
operation
1 0 to 15 minutes (n/a for Combi boiler)
P035P035
Pump modulation
1
0 = o
1 = on
P036P036
Anti-cycle time central heating
5
Delay time for central heating only 0 to 15 minutes
(this does not delay DHW production)
p040p040
Activate clock program CH operation 1
0 = inactive
1 = active
P057P057
Response for OpenTherm room thermostat 1
0 = do not respond to heat demand if requested
temperature is lower than 30°C
1 = respond to heat demand with minimum flow
temperature limited at 30°C
2 = respond to heat demand with maximum set flow
temperature (on/o function)
P059P059
Maximum setting value of flow temperature 80 10°C to 90°C
P070P070
Set maximum DHW output 100 20% to 100%
P074P074
Number ECO days (During pre-heat) 7 0 to 10 days
P075P075
Max flow temp during DHW production 80 60°C to 90°C
P077P077
Waiting time central heating demand aer
DHW operation
0 to 15 minutes
P081P081
Setting of three-way valve or electric shut-
o valve
0
0 = powered during central heating demand
1 = powered during DHW operation
p087p087
Activate clock program DHW operation 0
0 = inactive
1 = active
9.3 Parameters
1
DHW comfort function o.