GD200A series VFD Function parameters
-47-
Function
code
Name
Description
Default
value
Modify
P02.08
Leakage
inductance of
AM 1
0.16553.5mH
automatically. In static
self-learning mode 2, the settings
of P02.06P02.08 can be
updated automatically. These
parameters are the basic
parameters for the VFD to control
the motor and have direct impact
on control performance.
Note: Exercise caution before
modifying these parameters.
Depend
on
model
P02.09
Mutual
inductance of
AM 1
0.16553.5mH
Depend
on
model
P02.10
Non-load
current of AM 1
0.16553.5A
Depend
on
model
P02.26
Motor 1
overload
protection
0: No protection
1: Common motor (with low speed compensation).
Because the heat-releasing effect of the common
motors will be weakened, the corresponding
electric heat protection will be adjusted properly.
The low speed compensation characteristic
mentioned here means reducing the threshold of
the overload protection of the motor whose
running frequency is below 30Hz.
2: Variable frequency motor (without low speed
compensation) Because the heat-releasing effect
of the specific motors won’t be impacted by the
rotation speed, it is not necessary to adjust the
protection value during low-speed running.
2
P02.27
Motor 1 over
load protection
coefficient
Times of motor overload M = Iout/(In*K)
In is the rated current of the motor, Iout is the
output current of the VFD and K is the motor
protection coefficient.
So, the bigger the value of K is, the smaller the
value of M is. When M=116%, protection is
performed after motor overload lasts for 1 hour;
when M=150%, protection is performed after
motor overload lasts for 12 minutes; when
M=180%, protection is performed after motor
overload lasts for 5 minutes; when M=200%,
protection is performed after motor overload lasts
for 60 seconds; and when M≥ 400%, protection is
performed immediately.
100.0%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive200A Series and is the answer not in the manual?

INVT Goodrive200A Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive200A Series
CategoryDC Drives
LanguageEnglish

Related product manuals