status.measurement.instrument.smuX.*
This attribute contains the registers of the measurement event SMU X summary register set.
Type TSP-Link accessible Affected by Where saved Default value
Attribute
- -
- -
- -
- -
.condition (R)
Yes
Not applicable
Not saved
Not applicable
.enable (RW)
Yes
Status reset
Not saved
0
.event (R) Yes Status reset Not saved 0
.ntr (RW)
Yes
Status reset
Not saved
0
.ptr (RW)
Yes
Status reset
Not saved
387 (All bits set)
Usage
measurementRegister = status.measurement.instrument.smuX.condition
measurementRegister = status.measurement.instrument.smuX.enable
measurementRegister = status.measurement.instrument.smuX.event
measurementRegister = status.measurement.instrument.smuX.ntr
measurementRegister = status.measurement.instrument.smuX.ptr
status.measurement.instrument.smuX.enable = measurementRegister
status.measurement.instrument.smuX.ntr = measurementRegister
status.measurement.instrument.smuX.ptr = measurementRegister
measurementRegister
The status of the instrument measurement status SMU X summary register; a
zero (0) indicates no bits set (also send 0 to clear all bits); other values indicate
various bit settings
X
Source-measure unit (SMU) channel (for example
status.measurement.instrument.smua.enable applies to SMU
channel A)
Details
These attributes are used to read or write to the measurement event SMU X summary registers. Reading a
status register returns a value. The binary equivalent of the returned value indicates which register bits are set.
The least significant bit of the binary number is bit B0, and the most significant bit is bit B15. For example,
assume the value 257 is returned for the enable register. The binary equivalent is 0000 0001 0000 0001. This
value indicates that bit B0 (VLMT) and bit B8 (BAV) are set.
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
**
>
>
>
>
>
>
>
>
>
>
>
>
>
>
*
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
1
* Least significant bit
** Most significant bit

Table of Contents

Other manuals for Keithley 2614B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Keithley 2614B and is the answer not in the manual?

Keithley 2614B Specifications

General IconGeneral
BrandKeithley
Model2614B
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals