AIF3_IO_AutomationInterface (node number 43)
Outputs_AIF3
13
273
EDBCSXA064 EN 3.2
13.4.2 Outputs_AIF3
This SB is used as an interface for output signals (e.g. setpoints/actual values) to attached
fieldbus modules (e.g. INTERBUS, PROFIBUS−DP).
The process image is
ƒ created in the cyclic task by means of a fixed set time interval of 10 ms.
ƒ created in an interval task within the time set for this task.
ƒ read at the beginning of the task and written at its end.
Please read the documentation for the connected fieldbus module.
...
Byte
1
Byte
2
Byte
3
Byte
4
Byte
5
Byte
6
Byte
7
Byte
8
...
16 Bit
LowWord
16 Bit
HighWord
16 Bit
16 binary
signals
16 Bit
16 binary
signals
16 Bit
16 Bit
Outputs_AIF3
X1
AIF3_nOutW2_a
AIF3_nOutW1_a
AIF3_bFDO0_b
AIF3_bFDO15_b
AIF3_bFDO16_b
AIF3_bFDO31_b
AIF3_nOutW4_a
AIF3_dnOutD1_p
AIF3_nOutW3_a
ECSXA206
Fig. 13−8 System block "Outputs_AIF3"
System variables
Variable Data
type
Signal
type
Address Display
code
Display
format
Notes
AIF3_nOutW1_a
Integer
analog
%QW43.0
˘ ˘
AIF3_nOutW2_a %QW43.1
AIF3_nOutW3_a %QW43.2
AIF3_nOutW4_a %QW43.3
AIF3_bFDO0_b
...
AIF3_bFDO15_b
BOOL binary
%QX43.0.0
...
%QX43.0.15
˘ ˘
AIF3_bFDO16_b
...
AIF3_bFDO31_b
%QX43.1.0
...
%QX43.1.15
AIF3_dnOutD1_p
Double
integer
position %QD43.0 ˘ ˘

Table of Contents

Other manuals for Lenze ECSxK001 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze ECSxK001 series and is the answer not in the manual?

Lenze ECSxK001 series Specifications

General IconGeneral
BrandLenze
ModelECSxK001 series
CategoryControl Unit
LanguageEnglish

Related product manuals