63
Configuration with the CFG-300 LCD Service Tool
Select Features to access the Feature Config menu shown in Figure 40.
Figure 40 Feature Config menu
Table 14 describes the options in the Feature Config menu.
Table 14 Feature Config menu
Feature Default
Name in the
FA-300
Configuration Utility
Description
Command Menu/FA-300 Config/Features/
1. Manual Signal Silence
[X] ENABLE->Default
[ ] DISABLE
Manual signal silence
Use this menu to enable or
disable the SIGNAL SILENCE
button. See 9.4.2 SIGNAL
SILENCE Button on page 48.
Command Menu/FA-300 Config/Features/
2.Fire Drill
[X] ENABLE ->Default
[ ] DISABLE
Fire drill
Use this menu to enable or
disable the FIRE DRILL button.
See 9.4.3 FIRE DRILL Button on
page 48.
- Feature Config -
1 Man. Sig. Sil.
2 Fire Drill
3 Opt. Ckt. Corr
4 Wtr/Sprk. Retd
5 Aux Disc Prog
6 Sig-Sil Inh Tm
7 Aux Dis, Alm&Sup
8 Auto Sil. Tmr
9 Rem. Annun.
10 Alm. Xmit-Sil.
11 Pwr Fail Tmr.
12 Com. Supv. Rly
13 Sig-Sil. Isol.
14 Strobe Type
15 Signal Rate
16 Active EOL
17 Two Stage Op.
18 Gen-Alm Tmr
19 Com Alm Rly Op
20 1st stage LED ind
Manual Sig. Silence
[X] ENABLE