Appendix B: Reporting
13.2 Security Industries Association SIA-DCS
SIA protocol does not define indicating zone troubles, but lists it as Untyped Zone Trouble/
Restore.
13.2.1 FA-300 Event Codes
Event Description Event Family Qualifier SIA Event
Code
Parameter
Phone Line #1 trouble detected Trouble New event LT 001
Phone Line #2 trouble detected Trouble New event LT 002
Phone Line #1 trouble restored Trouble Restore LR 001
Phone Line #2 trouble restored Trouble Restore LR 002
Failure to report to an Account Trouble New event RT Acct #
Report to an Account successful Trouble Restore YK Acct #
Periodic (24 hr) Test Event (Normal) Test New event RP 000
Periodic (24 hr) Test Event (Off-normal) Test New event RY 000
Manually initiated dialer test Test New event RX 000
Zone Fire Alarm Alarm New event FA 000
Zone Fire Alarm restored Alarm Restore FH 000
Zone Trouble detected Trouble New event FT 000
Zone Trouble restored Trouble Restore FJ 000
Zone Supervisory condition Supervisory New event FS 000
Zone Supervisory restored Supervisory Restore FR 000
Waterflow alarm Alarm New event WA 000
Waterflow alarm restored Alarm Restore WH 000
Indicating Zone Trouble (*) Trouble New event UT 000
Indicating Zone Trouble restored (*) Trouble Restore UR 000
AC power lost Trouble New event AT 000
AC power restored Trouble Restore AR 000
Battery Low Trouble New event YT 000
Battery Low restored Trouble Restore YR 000
Ground Fault Trouble New event YP 000
Ground Fault restored Trouble Restore YQ 000

Table of Contents

Other manuals for Mircom FA-301-12LDR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom FA-301-12LDR and is the answer not in the manual?

Mircom FA-301-12LDR Specifications

General IconGeneral
BrandMircom
ModelFA-301-12LDR
CategoryControl Panel
LanguageEnglish

Related product manuals