FX Series Programmable Controller Diagnostic Devices 6
6-13
6.8 Error Detection Devices
(M8060 to M8069 and D8060 to D6069)
For symbol key see page 6-1.
• Please see the following page for the notes referenced in this table.
Diagnostic
Device
Operation
Diagnostic
Device
Operation
Detection
PROG.E
LED
PLC
STATUS
ON-
OFF
OFF
-ON
Other
M8060 (
7)
I/O
configuration
error
(Not FX1S,FX1N)
üü
While the
PLC is in
RUN
OFF RUN
D8060 (7)
(Not FX1S,FX1N)
The first I/O number of
the unit or block causing
the error - See note 6
M8061 (
7)
PLC hardware
error
ü
-
ON STOP
D8061 (7)
Error code for hardware
error - See appropriate
error code table
M8062 (
7)
PC/HPP
comms error on
programming
port
(Not FX1S,FX1N)
--
When a
signal from
the
programming
port is
received
OFF RUN
D8062 (7)
(Not FX1S,FX1N)
Error code for PC/HPP
Communications error -
See appropriate error
code table
M8063(
7)(-R)
Parallel link/
RS232-C and
RS485 (422)
comms error on
optional port
When a
signal from
the optional
port is
received
D8063(7)(-R)
Error code for parallel
link error - See FX
communication users
manual
M8064 (
7)
Parameter
error
üü
When the
program is
changed
(PLC in
STOP) and
when a
program is
transferred
(PLC in
STOP)
Flash STOP
D8064 (7)
Error code identifying
parametererror-See
appropriate error code
table
M8065 (
7)
Syntax error
D8065 (
7)
Error code identifying
syntax error - See
appropriate error code
table
M8066 (
7)
Program
error
D8066 (
7)
Error code identifying
program construction
error
See appropriate error
code table
M8067(
7)(-R)
Operation
error
--
While in PLC
is in RUN
OFF RUN
D8067(7)(-R)
Error code identifying
operation error. See
appropriate error code
table
M8068 (-)
Operation
error latch
D8068 (-)
Operation error step
number latched
M8069 (-)
I/O bus error
(Not FX1S,FX1N)
See note 7
- - D8069(7)(-R)
Step numbers for found
errors corresponding to
flags M8065 to M8067
FX
1S
FX
1N
FX
2N
FX2NC